| Plan Review Notes For Permit 04060853 |
| Permit Number |
04060853 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-08-17 00:00:00 | ************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE SOME NOTES FROM FIRST | | | REVIEW STILL NEED TO BE ADDRESSED. | | | | | | 2)NOTE: PLEASE SEE FAC 61G15-23.002 AND | | | FS 471.023,025. | | | PLEASE INCLUDE ALL REQUIRED INFORMATION | | | ON TITLE BLOCKS AS REQUIRED PER ABOVE. | | | PLEASE ALSO SEE PLANS ARE NOT SIGNED, | | | DATED AND SEALED BY THE ENGINEER OF | | | RECORD. | | | | | | 3)NOTE: PLEASE SEE PANEL SCHEDULE NOW | | | SUBMITTED ALONG W/ LOAD CALCS WHICH ARE | | | BOTH SHOWN "BLANK". THE NOTE MENTIONS | | | CONTRACTOR TO BE RESPONSIBLE FOR THIS, | | | HOWEVER MIN REQUIREMENTS UNDER 2002 NEC | | | IS REQUIRED AT THIS TIME. | | | 215.5/220.31B | | | | | | 4)NOTE: PLEASE INCLUDE RISER DIAGRAM | | | WHICH FEEDS DETACHED BLDG. | | | PLANS DO NOT INDICATE HOW THIS BLDG IS | | | FED/ GROUNDING /PANEL SCHEDULE ETC. | | | 225.31,250.32. | | | | | | 5)NOTE: PLEASE SEE PLANS INDICATE AN | | | EXISTING A/C CU, YET SHOWS A NEW AHU? | | | PLEASE CLARIFY. | | | PLANS/ APPLICATION MENTIONS CONVERTING | | | AN EXSITING GARAGE? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|