2004-08-17 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SEE SOME NOTES FROM FIRST
 REVIEW STILL NEED TO BE ADDRESSED.
  
 2)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 FS 471.023,025.
 PLEASE INCLUDE ALL REQUIRED INFORMATION
 ON TITLE BLOCKS AS REQUIRED PER ABOVE.
 PLEASE ALSO SEE PLANS ARE NOT SIGNED,
 DATED AND SEALED BY THE ENGINEER OF
 RECORD.
  
 3)NOTE: PLEASE SEE PANEL SCHEDULE NOW
 SUBMITTED ALONG W/ LOAD CALCS WHICH ARE
 BOTH SHOWN "BLANK". THE NOTE MENTIONS
 CONTRACTOR TO BE RESPONSIBLE FOR THIS,
 HOWEVER MIN REQUIREMENTS UNDER 2002 NEC
 IS REQUIRED AT THIS TIME.
 215.5/220.31B
  
 4)NOTE: PLEASE INCLUDE RISER DIAGRAM
 WHICH FEEDS DETACHED BLDG.
 PLANS DO NOT INDICATE HOW THIS BLDG IS
 FED/ GROUNDING /PANEL SCHEDULE ETC.
 225.31,250.32.
  
 5)NOTE: PLEASE SEE PLANS INDICATE AN
 EXISTING A/C CU, YET SHOWS A NEW AHU?
 PLEASE CLARIFY.
 PLANS/ APPLICATION MENTIONS CONVERTING
 AN EXSITING GARAGE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  