2004-08-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) FROM PREVIOUS REVIEW:
 2 SETS OF PLANS WITH DBPR STAMP AND WORK
 SHEET ARE REQUIRED FOR REVIEW. SECTION
 104.2.1. - ONLY ONE SET OF PLANS AND
 WORK SHEET SUBMITTED. - ALSO FROM PRE-
 VIOUS REVIEW: SHEETS ADDED TO PLANS WITH
 DBPR STAMP ON THEM SHALL BE SIGNED,
 SEALED, AND DATED BY THE ENGINEER OF
 RECORD AS REQUIRED BY SECTION 104.2.2.
 2) FROM PREVIOUS REVIEW: CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE FOR SIZ-
 ING OF GREASE INTECEPTOR. WASTE ORDIN.
 #2938-96. (561) 837-4074. NO RESPONSE
 NOTED.
 3) SHT A1.1 EQUIPMENT SCHEDULE:
 #23 (2) HAND SINKS, NO WATER SUPPLY OR
 DRAINAGE INDICATED ON SCHEDULE.
 #24 3 HOLE STEAM TABLE, NO DRAIN? PLEASE
 CLARIFY. SECTION 104.2.1
 THESE COMMENTS WERE NOT ADDRESSED.
 4) FROM PREVIOUS REVIEW: FOR GAS
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES. - NOT ALL
 PIPE SIZES SHOWN. ALSO SHUT OFF VALVES
 SHALL BE THE SAME SIZE AS THE PIPE SIZE
 REQUIRED FOR GAS APPLIANCE. - PIPES
 SHALL BE SIZED PER FBC-2001 FUEL GAS
 TABLE 402(26)
  
 REVIEW BY KEN STEVENS