Plan Review Notes
Plan Review Notes For Permit 04060851
Permit Number 04060851
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A1.0 MEN & WOMEN TOILET ROOMS,
 SHOW CLEAR FLOOR SPACE FOR W/C'S PER FIG
 28. MINIMUM 48" WIDE CLEAR FLOOR SPACE.
 URINAL PARTITION SHOWN IN URINAL DETAIL
 CAN NOT BE IN CLEAR FLOOR SPACE FOR THE
 WATER CLOSET. SECTION 11-4.22.3
 2) 2 SETS OF PLANS WITH DBPR STAMP AND
 WORK SHEETS ARE REQUIRED FOR REVIEW.
 SECTION 104.2.1
 3) CONTACT RODNEY COMPO ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF GREASE INTECEP-
 TOR. WASTE ORD. #2938-96. (561) 837-4074
 4) SEE ATTACHED SHEET FOR UTILITY STAND-
 ARD FOR GREASE INTERCEPTORS.
 5) SHT A1.1 EQUIPMENT SCHEDULE:
 #19.9 REFRIDGERATION FOR #18? (MOP SINK)
 PLEASE CLAIRFY. SECTION 104.2.1
 #23 (2) HAND SINKS, NO WATER SUPPLYS OR
 DRAINAGE INDICATED ON SCHEDULE?
 #24 3 HOLE STEAM TABLE, NO DRAIN?
 PLEASE CLARIFY. SECTION 104.2.1
 6) SHT A3.0 GREASE RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE MOP SINK
 AND FLOOR SINK FOR THE ICE MAKER ARE NOT
 SHOWN ON RISER. SECTION 104.2.1
 7) SHT A3.0 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9 SHALL BE LOCATED NEAR THE FIXTURES
 NOT IN THE CEILING. PDI-WH 201.
 8) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 9) THERMAL EXPANSION CONTROL IS REQUIRED
 FOR THE WATER HEATER. SECTION 607.3.2.
 10) THE FOLLOWING INFORMATION IS REQUIR-
 ED FOR GAS PERMIT. SEPARATE GAS PERMIT
 REQUIRED.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - NOT ALL MEASUREMENTS
 ARE SHOWN.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. - THE MAN-
 UAL VALVE IS SHOWN DOWNSTREAM OF THE
 EMERGENCY VALVE.
 11) ENG'S SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025 - REMOVE
 ALL REFERENCES TO METRO DESIGN GROUP
 FROM THE PLANS.
 12) SHEETS ADDED TO PLANS WITH DBPR
 STAMP ON THEM SHALL BE SIGNED AND SEALED
 BY THE ENGINEER OF RECORD AS REQUIRED
 BE SECTION 104.2.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]