| 2004-07-09 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHT A1.0 MEN & WOMEN TOILET ROOMS, |
| | SHOW CLEAR FLOOR SPACE FOR W/C'S PER FIG |
| | 28. MINIMUM 48" WIDE CLEAR FLOOR SPACE. |
| | URINAL PARTITION SHOWN IN URINAL DETAIL |
| | CAN NOT BE IN CLEAR FLOOR SPACE FOR THE |
| | WATER CLOSET. SECTION 11-4.22.3 |
| | 2) 2 SETS OF PLANS WITH DBPR STAMP AND |
| | WORK SHEETS ARE REQUIRED FOR REVIEW. |
| | SECTION 104.2.1 |
| | 3) CONTACT RODNEY COMPO ENVIRONMENTAL |
| | COMPLIANCE FOR SIZING OF GREASE INTECEP- |
| | TOR. WASTE ORD. #2938-96. (561) 837-4074 |
| | 4) SEE ATTACHED SHEET FOR UTILITY STAND- |
| | ARD FOR GREASE INTERCEPTORS. |
| | 5) SHT A1.1 EQUIPMENT SCHEDULE: |
| | #19.9 REFRIDGERATION FOR #18? (MOP SINK) |
| | PLEASE CLAIRFY. SECTION 104.2.1 |
| | #23 (2) HAND SINKS, NO WATER SUPPLYS OR |
| | DRAINAGE INDICATED ON SCHEDULE? |
| | #24 3 HOLE STEAM TABLE, NO DRAIN? |
| | PLEASE CLARIFY. SECTION 104.2.1 |
| | 6) SHT A3.0 GREASE RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN. THE MOP SINK |
| | AND FLOOR SINK FOR THE ICE MAKER ARE NOT |
| | SHOWN ON RISER. SECTION 104.2.1 |
| | 7) SHT A3.0 WATER RISER DIAGRAM, WATER |
| | HAMMER ARRESTORS REQUIRED BY SECTION |
| | 604.9 SHALL BE LOCATED NEAR THE FIXTURES |
| | NOT IN THE CEILING. PDI-WH 201. |
| | 8) AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE. SECTION 608.13.2 |
| | 9) THERMAL EXPANSION CONTROL IS REQUIRED |
| | FOR THE WATER HEATER. SECTION 607.3.2. |
| | 10) THE FOLLOWING INFORMATION IS REQUIR- |
| | ED FOR GAS PERMIT. SEPARATE GAS PERMIT |
| | REQUIRED. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. - NOT ALL MEASUREMENTS |
| | ARE SHOWN. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | E. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. - THE MAN- |
| | UAL VALVE IS SHOWN DOWNSTREAM OF THE |
| | EMERGENCY VALVE. |
| | 11) ENG'S SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) - FS 471.025 - REMOVE |
| | ALL REFERENCES TO METRO DESIGN GROUP |
| | FROM THE PLANS. |
| | 12) SHEETS ADDED TO PLANS WITH DBPR |
| | STAMP ON THEM SHALL BE SIGNED AND SEALED |
| | BY THE ENGINEER OF RECORD AS REQUIRED |
| | BE SECTION 104.2.2. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |