| Plan Review Notes For Permit 04060851 |
| Permit Number |
04060851 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-06 00:00:00 | DENIED: | | | 1.PLAN SHEET A3.0 INDICATES LP TANKS | | | ARE EXISTING WHEREAS PLAN SHEET A3.1 | | | INDICATES LP TANKS BY THE UTILITY CO. | | | PLEASE CLARIFY. | | | | | | 2.INDICATE CAPACITY OF THE TANKS, | | | DISTANCE FROM THE PROPERY LINE, BUILDING | | | AND COMBUSTIBLES.SHOW COMPLIANCE WITH | | | NFPA 58. | | | | | | 3.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | 2001 FBC(M) 403.3. | | | | | | 4.ADDITIONAL PERMITS REQUIRED FOR THE | | | HOODS, FIRE SUPPRESSION AND WALK-IN | | | COOLERS.PLEASE PROVIDE PLANS AND | | | MANUFACTURER SUBMITTAL DATA WITH PERMIT | | | APPLICATION. | | | | | | 5.PLEASE SEE COMMENT #1 BY DEWEY | | | PALMER, ELECTRICAL PLAN REVIEW.PROVIDE | | | CERTIFICATE OF AUTHORIZATION # AS | | | REQUIRED BY FS 471.023 & FAC 61G15.23.00 | | | .2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|