| Notes |
| Date |
Text |
| 2004-06-18 00:00:00 | 1) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 2) PLEASE PROVIDE MORE DETAILS ON LP | | | GAS TANKS. WHAT SIZE, HOW CLOSE TO | | | PROPERTY LINES, WHAT MECHANICAL | | | PROTECTION IS PROVIDED, AND ARE THE | | | TANKS PROPERLY LABELED. | | | | | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR HOOD, DUCT, AND FIRE SUPPRESSION | | | SYSTEMS PLANNED FOR USE. | | | | | | 4) WHAT SIZES ARE THE PORTABLE FIRE | | | EXTINGUISHERS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|