| Plan Review Notes For Permit 04060837 |
| Permit Number |
04060837 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-08-10 00:00:00 | ********* PROVISO/REVISION ************* | | | | | | 1)NOTE: PLEASE SEE PLANS NOW INDICATE | | | TWO PANELS? PLANS ARE STILL NOT SHOWING | | | METER/SERVICE LOCATION AS REQUESTED ON | | | FIRST REVIEW. | | | | | | 2)NOTE: PLEASE SEE RISER NOW INDICATES | | | AN EQUIPMENT GROUNDING CONDUCTOR FROM | | | METER TO MAIN. PLEASE SEE 250.24,250.6 | | | AN EQUIPMENT GRND IS ONLY INSTALLED | | | AFTER THE FIRST MEANS OF DISCONNECT. | | | | | | 3)NOTE: PLEASE SEE " ELECTRICAL NOTES" | | | REFEERENCES ARC-FAULT PROTECTION FOR | | | RECEPTS ONLY. WE ARE UNDER 2002 NEC , | | | 210.12 WHICH REQUIRES AFCI PROTECTION | | | FOR ALL "OUTLETS" IN BEDRMS. | | | | | | PLEASE SUBMIT CORRECTED REVISED PLANS | | | BEFORE ANY ROUGH ELECTRICAL INSPECTION | | | IS CALLED IN. IF PLANS COME BACK FOR ANY | | | CORRECTIONS NEEDED BEFORE PERMIT IS | | | ISSUED, PLEASE MAKE CORRECTIONS AT THAT | | | TIME. | | | THIS WILL BE A REVISION AND FEES WILL BE | | | DUE AFTER PERMIT IS ISSUED. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|