Plan Review Notes
Plan Review Notes For Permit 04060837
Permit Number 04060837
Review Stop E
Sequence Number 2
Notes
Date Text
2004-08-10 00:00:00********* PROVISO/REVISION *************
  
 1)NOTE: PLEASE SEE PLANS NOW INDICATE
 TWO PANELS? PLANS ARE STILL NOT SHOWING
 METER/SERVICE LOCATION AS REQUESTED ON
 FIRST REVIEW.
  
 2)NOTE: PLEASE SEE RISER NOW INDICATES
 AN EQUIPMENT GROUNDING CONDUCTOR FROM
 METER TO MAIN. PLEASE SEE 250.24,250.6
 AN EQUIPMENT GRND IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE SEE " ELECTRICAL NOTES"
 REFEERENCES ARC-FAULT PROTECTION FOR
 RECEPTS ONLY. WE ARE UNDER 2002 NEC ,
 210.12 WHICH REQUIRES AFCI PROTECTION
 FOR ALL "OUTLETS" IN BEDRMS.
  
 PLEASE SUBMIT CORRECTED REVISED PLANS
 BEFORE ANY ROUGH ELECTRICAL INSPECTION
 IS CALLED IN. IF PLANS COME BACK FOR ANY
 CORRECTIONS NEEDED BEFORE PERMIT IS
 ISSUED, PLEASE MAKE CORRECTIONS AT THAT
 TIME.
 THIS WILL BE A REVISION AND FEES WILL BE
 DUE AFTER PERMIT IS ISSUED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]