Plan Review Notes
Plan Review Notes For Permit 04060837
Permit Number 04060837
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-22 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SEE SECOND SHEET MISSING
 REQUIRED TITLE BLOCK. FAC 61G15-23.002
  
 2)NOTE: PLEASE SEE PANEL IS SHOWN AS A
 125A W/ 4/0'S LISTED AS SEC'S? PLEASE
 SEE 310.15B6 4/0'S ARE RATED FOR A 250A
 SERVICE. THESE ARE PERMITTED TO BE
 INSTALLED BUT NOT REQUIRED TO THIS SIZE.
 THIS IS ONLY A NOTE: IF SHOWN,THEN THEY
 WILL BE REQUIRED.
  
 3)NOTE: PLEASE SEE PLANS ARE NOT SHOWING
 A/C UNITS, REQUIRED DISC'S, RECEPTS.
 440.11,210.63,210.70?
  
 4)NOTE:PLEASE SEE MISSING FRONT AND REAR
 RECEPTS. PER 210.52E
  
 5)NOTE: PLEASE SEE RECEPTS IN BEDRM ARE
 SHOWN AS AFI, HOWEVER WE AREUNDER THE
 2002 NEC WHICH REQUIRES PROTECTION FOR
 ALL "OUTLETS" INCLUDING SD'S/LTS/FANS.
 210.12
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 7)NOTE: PLEASE SHOW LOCATION OF METER
 ON HOUSE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]