| Plan Review Notes For Permit 04060837 |
| Permit Number |
04060837 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-22 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE SECOND SHEET MISSING | | | REQUIRED TITLE BLOCK. FAC 61G15-23.002 | | | | | | 2)NOTE: PLEASE SEE PANEL IS SHOWN AS A | | | 125A W/ 4/0'S LISTED AS SEC'S? PLEASE | | | SEE 310.15B6 4/0'S ARE RATED FOR A 250A | | | SERVICE. THESE ARE PERMITTED TO BE | | | INSTALLED BUT NOT REQUIRED TO THIS SIZE. | | | THIS IS ONLY A NOTE: IF SHOWN,THEN THEY | | | WILL BE REQUIRED. | | | | | | 3)NOTE: PLEASE SEE PLANS ARE NOT SHOWING | | | A/C UNITS, REQUIRED DISC'S, RECEPTS. | | | 440.11,210.63,210.70? | | | | | | 4)NOTE:PLEASE SEE MISSING FRONT AND REAR | | | RECEPTS. PER 210.52E | | | | | | 5)NOTE: PLEASE SEE RECEPTS IN BEDRM ARE | | | SHOWN AS AFI, HOWEVER WE AREUNDER THE | | | 2002 NEC WHICH REQUIRES PROTECTION FOR | | | ALL "OUTLETS" INCLUDING SD'S/LTS/FANS. | | | 210.12 | | | | | | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 7)NOTE: PLEASE SHOW LOCATION OF METER | | | ON HOUSE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|