| 2004-06-22 00:00:00 | ************ UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SEE 250.32 FOR GROUNDING |
| | ELECTRODE SYSTEM AT DETACHED BLDGS. |
| | PLEASE ALSO SEE MISSING EQUIPMENT GROUND |
| | -ING CONDUCTOR FROM 200A PANEL TO NEW |
| | 100A PANEL. |
| | |
| | 2)NOTE: PLEASE INDICATE MEANS OF DISC |
| | AT DEACHED BLDG. 225.31 |
| | MCB?DISCONNECT? |
| | |
| | 3)NOTE: PLEASE LIST OCP AT 200A PANEL |
| | FOR NEW FEED. |
| | |
| | 4)NOTE: PLEASE SEE HEAT SHOWN FOR A/C |
| | UNIT @ 6500 VA? THIS IS NOT A COMMON |
| | SIZE, PLEASE VERIFY THIS. |
| | PLEASE ALSO SEE 424.3B FOR OCP. |
| | |
| | 5)NOTE: PLEASE SEE 220.31B. PLEASE |
| | PROVIDE LOAD CALC FOR EXISTING AND NEW. |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SEE COUNTERSPACE IN |
| | KITCEHN AREA FOR RECEPT SPACING PER |
| | 210.52C1 |
| | |
| | 7)NOTE: PLEASE INDICATE LT/RECEPT FOR |
| | ATTIC STORAGE AREA/ AHU. 210.70,210.63 |
| | |
| | 8)NOTE: PLEASE SEE AREA IS CONSIDERED |
| | AN ADAPTABLE SLEEPING ROOM. ARC FAULT |
| | PROTECTION WILL BE REQUIRED FOR ALL |
| | "OUTLETS" IN THAT RM PER 210.12 2002 NEC |
| | A SD WILL ALSO BE REQUIRED PER NFPA-72 |
| | |
| | 9)NOTE: PLEASE VERIFY IF POOL EQUIPMENT |
| | SHOWN IS FED FROM A DIFERENT LOCATION? |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO TWO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |