| Plan Review Notes For Permit 04060786 |
| Permit Number |
04060786 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-23 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO, DURING AND AFTER CONSTRUCTION. | | | | | | 2) BUILDING ADDRESSES REQUIRED. | | | | | | 3) PRSCRIPTIVE STRENGTH REQUIREMENTS | | | SHALL BE SHOWN ON PLANS FOR ALL | | | HANDRAILS AND GUARDRAILS. | | | | | | 4) IS THE DOOR BETWEEN THE GARAGE AND | | | THE STAIRS RATED.NO RATING SHOWN ON DOOR | | | SCHEDULE. | | | | | | 5) SMOKE DETECTORS SHALL BE PLACED A | | | MINIMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | | | | 6) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. PAGE A.1 INDICATES THAT THE | | | BUILDING WILL BE FIRE SPRINKLER | | | PROTECTED. | | | | | | 7) NO INFORMATION PROVIDED REGARDING | | | MONITORING OF THE FIRE SPRINKLER SYSTEM. | | | | | | 8) SITE PLAN DOES NOT DIPLAY ANY FIRE | | | HYDRANTS. | | | | | | 9) NO MENTION OF ANY FIRE EXTINGUISHERS. | | | | | | COURTESY REVIEW PERFORMED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|