Plan Review Notes
Plan Review Notes For Permit 04060776
Permit Number 04060776
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-17 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE ONLY ONE SHEET OF
 EACH E0.1 IS IN ONE SET AND ONLY ONE
 SHEET E2.1 IN OTHER SET.
 PLEASE SUBMIT TWO COMPLETE SETS.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATION
 FOR EXSITING PANEL SBA.215.5
  
 3)NOTE: PLEASE VERIFY MEANS OF DISC AT
 ATS, PER 230.76, 230.79
  
 4)NOTE: PLEASE SEE PANEL BOARD ON SEC
 SIDE OF TRANSFORMER IS SHOWN AS MLO,
 PLEASE SEE 408-16D, 240-21C1 ETC MCB
 REQUIRED.
  
 3NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125%(LIGHTING ETC)(LARGEST MOTORS)
 215.2,215.3,230.42,210.19A,210.20A ETC
  
 4)NOTE: PLEASE INCLUDE LOCATION OF
 PANEL "H". IS THIS A HOUSE PANEL OR
 PANEL TO THIS SPACE.
 PLEASE ALSO SHOW SIZE OF EXSITING PANELS
 "D".
  
 5)NOTE: PLEASE SEE LICENSE # ON TITLE
 BLOCK IS NOT CORRECT. PLEASE SEE DBPR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]