| Plan Review Notes For Permit 04060776 |
| Permit Number |
04060776 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-17 00:00:00 | *********** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE ONLY ONE SHEET OF | | | EACH E0.1 IS IN ONE SET AND ONLY ONE | | | SHEET E2.1 IN OTHER SET. | | | PLEASE SUBMIT TWO COMPLETE SETS. | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATION | | | FOR EXSITING PANEL SBA.215.5 | | | | | | 3)NOTE: PLEASE VERIFY MEANS OF DISC AT | | | ATS, PER 230.76, 230.79 | | | | | | 4)NOTE: PLEASE SEE PANEL BOARD ON SEC | | | SIDE OF TRANSFORMER IS SHOWN AS MLO, | | | PLEASE SEE 408-16D, 240-21C1 ETC MCB | | | REQUIRED. | | | | | | 3NOTE: PLEASE SHOW ALL CONTINUOUS LOAD | | | -S AT 125%(LIGHTING ETC)(LARGEST MOTORS) | | | 215.2,215.3,230.42,210.19A,210.20A ETC | | | | | | 4)NOTE: PLEASE INCLUDE LOCATION OF | | | PANEL "H". IS THIS A HOUSE PANEL OR | | | PANEL TO THIS SPACE. | | | PLEASE ALSO SHOW SIZE OF EXSITING PANELS | | | "D". | | | | | | 5)NOTE: PLEASE SEE LICENSE # ON TITLE | | | BLOCK IS NOT CORRECT. PLEASE SEE DBPR. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|