| 2004-06-24 00:00:00 | ************ UNSAT ************** |
| | BLDG # 4 |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. |
| | |
| | 2)NOTE: PLEASE SEE NFPA-72 FOR SD |
| | LOCATIONS. 3' FROM BATHS/KITCHENS AND |
| | 20' FROM COOKING APPLIANCES W/ EXCEPTION |
| | -S. 8-1.4.2 |
| | |
| | 3)NOTE: PLEASE INDICATE/SHOW AC, CU |
| | DISCONNECTS PER 440.11 |
| | |
| | 4)NOTE: PLEASE SEE E-8 FOR MISPRINT OF |
| | 210.12 FOR ARC FAULT ART. 2002 NEC. |
| | |
| | 5)NOTE: PLEASE SEE OCP SHOWN FOR AHU |
| | IS MUCH LARGER THAN OCP FOR CU, YET |
| | LOAD FOR CU IS SHOWN ON LOAD CALCS? |
| | PLEASE VERIFY AND CORRELATE WITH |
| | MECH PLANS. |
| | |
| | 6)NOTE: PLEASE SEE FS 471.023, FAC |
| | 61G15-23.002 FOR REQUIRED LICENSE #'S |
| | ON TITLE BLOCK.PLEASE SEE ATTACHED |
| | PRINT-OUT FROM DBPR WHICH INDICATES |
| | FIRM AS SHOWN ON TITLE BLOCK AS LICENSE |
| | BEING "CLOSED"? |
| | PLEASE NOTE, THIS # WAS NOT ON TITLE |
| | BLOCK. |
| | PLEASE ALSO SEE THE ABOVE IS REQUIRED |
| | OF ALL SHEETS AND TRADES WHEATHER OR |
| | NOT COMMENT IS MADE FROM OTHER REVIEWERS |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |