| 2005-02-14 00:00:00 | ******** UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE REDLINES FROM | | | PREVIOUS REVIEWS. | | | | | | 2)NOTE: PLEASE SEE OCP ON PANEL FOR | | | WHIRLPOOL 30A ON #12. | | | | | | 3)NOTE: PLEASE SEC'S TO BE SIZED PER | | | 310.15B6, 240.4. MIN 400 MCM | | | | | | 4)NOTE: PLEASE SEE GUTTER SIZING PER 366 | | | SHOWS 3"? | | | | | | 5)NOTE: PLEASE SEE FBC 104.2.1, WHICH | | | REQUIRES THE PRINTED NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR PLANS. | | | REQUIRED FOR ALL | | | | | | 6)NOTE: PLEASE ALSO SEE MISSING FOOTER | | | STEEL REQUIRED AS PART OF THE GROUNDING | | | ELECTRODE SYSTEM. 250.50 | | | | | | 7)NOTE: PLEASE SEE LETTER FROM ARCHITECT | | | IS ALSO REQUIRED TO BE NOTORIZED. | | | | | | PLEASE SEE PLANS REQUIRE A REVISION FEE | | | FOR REVISED SHEETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|