Plan Review Notes
Plan Review Notes For Permit 04060707
Permit Number 04060707
Review Stop E
Sequence Number 4
Notes
Date Text
2005-02-14 00:00:00******** UNSAT **********
  
 1)NOTE: PLEASE SEE REDLINES FROM
 PREVIOUS REVIEWS.
  
 2)NOTE: PLEASE SEE OCP ON PANEL FOR
 WHIRLPOOL 30A ON #12.
  
 3)NOTE: PLEASE SEC'S TO BE SIZED PER
 310.15B6, 240.4. MIN 400 MCM
  
 4)NOTE: PLEASE SEE GUTTER SIZING PER 366
 SHOWS 3"?
  
 5)NOTE: PLEASE SEE FBC 104.2.1, WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS.
 REQUIRED FOR ALL
  
 6)NOTE: PLEASE ALSO SEE MISSING FOOTER
 STEEL REQUIRED AS PART OF THE GROUNDING
 ELECTRODE SYSTEM. 250.50
  
 7)NOTE: PLEASE SEE LETTER FROM ARCHITECT
 IS ALSO REQUIRED TO BE NOTORIZED.
  
 PLEASE SEE PLANS REQUIRE A REVISION FEE
 FOR REVISED SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]