| Plan Review Notes For Permit 04060707 |
| Permit Number |
04060707 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-08-23 00:00:00 | *** NOTES REDLINED. *** | | | | | | SOME ITEMS FOR LOAD AND OCP WERE RED- | | | -LINED ON PANEL SCHEDULE. | | | | | | GUTTER SIZE TO METT NEC 366. | | | | | | GEC SHOWN TO SLAB, 250.50 REQUIRED TO | | | FOOTER STEEL. | | | | | | A COUPLE OF RECEPTS MISSING FOR 2' OF | | | WALL SPACE PER 210.52. REDLINED. | | | | | | SEC'S PER 310.15B6,240.4B |
|