Plan Review Notes
Plan Review Notes For Permit 04060707
Permit Number 04060707
Review Stop E
Sequence Number 2
Notes
Date Text
2004-08-23 00:00:00*** NOTES REDLINED. ***
  
 SOME ITEMS FOR LOAD AND OCP WERE RED-
 -LINED ON PANEL SCHEDULE.
  
 GUTTER SIZE TO METT NEC 366.
  
 GEC SHOWN TO SLAB, 250.50 REQUIRED TO
 FOOTER STEEL.
  
 A COUPLE OF RECEPTS MISSING FOR 2' OF
 WALL SPACE PER 210.52. REDLINED.
  
 SEC'S PER 310.15B6,240.4B