Plan Review Notes
Plan Review Notes For Permit 04060707
Permit Number 04060707
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-23 00:00:00************* UNSAT ************
  
 1)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE ALSO SEE ADAPTABLE RMS W/ CLOSETS
 OR BATHS ATTACHED.
  
 2) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 3) NOTE: PLEASE SEE 210.52C1,2,3 FOR
 RECEPT SPACING IN KITCHENS.THERE ARE A
 COUPLE MISSING. WALL/ PENINSULAR.
  
 4 )NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER PER 220.30
 PLEASE SEE LOAD FOR SUB-PANEL MUST BE
 FIGURED AND THEN ADDED TO MAIN PANEL.
 PLEASE SEE OTHER NOTES PERTAINING TO MIN
 LOADS FOR LAUNDRY ETC.
  
 5)NOTE: PLEASE SEE 220.16B, ETC
 FOR LAUNDRY LOAD MIN.
  
 6)NOTE: PLEASE CORRELATE LOAD/OCP FOR
 PUMPS ON PANEL SCHEDULE.
  
 7)NOTE:PLEASE SEE LOAD SHOWN ON PANEL
 "B" SCHEDULE DOES NOT CORRELATE WITH
 LOAD SHOWN ON PANEL "A" FOR PANEL "B".
  
 8)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS PER 2002 NEC
 210.12. THIS IS FOR ALL ITEMS IN BEDRMS.
 SD'S , LTS, FANS, RECEPTS.
  
 9)NOTE: PLEASE INDICATE REQUIRED GFI
 PROTECTION FOR WHIRLPOOL TUB. 680
  
 10)NOTE: PLEASE SEE SIZE OF DISCONNECT
 AND OCP FOR CU-3, SHOWS 65A DISC AND 65A
 OCP. PLEASE SEE PANEL SCHEDULE.?
  
 11)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS ON RISER.
 PANEL 'A' TO PANEL 'B' AND A/C EQUIP.
 210.110,250.122
  
 12)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250.66
  
 13)NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE ATTACHMENT TO FOOTER STEEL
 AS REQUIRED UNDER 250.50.
  
 14)NOTE: PLEASE SEE MISSING SEC'S SIZE
 FROM METER TO MAIN PANEL.
 PLEASE ALSO LABEL SIZE OF METER CAN.
  
 15)NOTE:PLEASE VERIFY SIZE OF CONDUCTOR
 SHOWN FOR 30A COOKTOP. SHOWS #6 FOR THIS
 UNLESS SOME SORT OF ADAPTER IS USED,
 #6 WILL NOT FIT A 2P30A BRKR.
 PLEASE VERIFY.
  
 16)NOTE: PLEASE SEE 210.52 FOR REQUIRED
 RECEPT SPACING IN HOUSE. THERE ARE A
 NUMBER OF MISSING RECEPTS. PLEASE SEE
 ONE SET OF PLANS HAS MOST OF THEM
 REDLINED, BUT EXACT LOCATIONS ARE NOT
 SPECIFIED. PLEASE ALSO SEE LEISURE "RM"
 RAILING AREA IS CONSIDERED "WALL SPACE"
 AND WILL REQUIRE RECEPTS PER 210.52.
  
 17)NOTE: PLEASE SEE 210.52D, GFI RECEPT
 FOR BATHS ARE REQUIRED TO BE WITHIN
 3' OF THE EDGE OF SINK. PLEASE SEE
 "HER" BATH AREA.
  
 18)NOTE: PLEASE SEE FS 471, 481.FAC
 61G15-23
 PLEASE SEE PLANS THAT CONTAIN A TITLE
 BLOCK OF AN ARCH/ ENGINEERMUST BE
 SIGNED, DATED AND SEALED BY THAT
 ENGINEER/ OR ARCH.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD MAY BE REQUIRED FOR
 REFERENCE BY SOME PLAN REVIEWERS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]