| Date |
Text |
| 2004-06-23 00:00:00 | ************* UNSAT ************ |
| | |
| | 1)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | PLEASE ALSO SEE ADAPTABLE RMS W/ CLOSETS |
| | OR BATHS ATTACHED. |
| | |
| | 2) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 3) NOTE: PLEASE SEE 210.52C1,2,3 FOR |
| | RECEPT SPACING IN KITCHENS.THERE ARE A |
| | COUPLE MISSING. WALL/ PENINSULAR. |
| | |
| | 4 )NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | PER PER 220.30 |
| | PLEASE SEE LOAD FOR SUB-PANEL MUST BE |
| | FIGURED AND THEN ADDED TO MAIN PANEL. |
| | PLEASE SEE OTHER NOTES PERTAINING TO MIN |
| | LOADS FOR LAUNDRY ETC. |
| | |
| | 5)NOTE: PLEASE SEE 220.16B, ETC |
| | FOR LAUNDRY LOAD MIN. |
| | |
| | 6)NOTE: PLEASE CORRELATE LOAD/OCP FOR |
| | PUMPS ON PANEL SCHEDULE. |
| | |
| | 7)NOTE:PLEASE SEE LOAD SHOWN ON PANEL |
| | "B" SCHEDULE DOES NOT CORRELATE WITH |
| | LOAD SHOWN ON PANEL "A" FOR PANEL "B". |
| | |
| | 8)NOTE: PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS PER 2002 NEC |
| | 210.12. THIS IS FOR ALL ITEMS IN BEDRMS. |
| | SD'S , LTS, FANS, RECEPTS. |
| | |
| | 9)NOTE: PLEASE INDICATE REQUIRED GFI |
| | PROTECTION FOR WHIRLPOOL TUB. 680 |
| | |
| | 10)NOTE: PLEASE SEE SIZE OF DISCONNECT |
| | AND OCP FOR CU-3, SHOWS 65A DISC AND 65A |
| | OCP. PLEASE SEE PANEL SCHEDULE.? |
| | |
| | 11)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS ON RISER. |
| | PANEL 'A' TO PANEL 'B' AND A/C EQUIP. |
| | 210.110,250.122 |
| | |
| | 12)NOTE: PLEASE SIZE GROUNDING ELECTRODE |
| | CONDUCTOR PER 250.66 |
| | |
| | 13)NOTE: PLEASE SEE MISSING GROUNDING |
| | ELECTRODE ATTACHMENT TO FOOTER STEEL |
| | AS REQUIRED UNDER 250.50. |
| | |
| | 14)NOTE: PLEASE SEE MISSING SEC'S SIZE |
| | FROM METER TO MAIN PANEL. |
| | PLEASE ALSO LABEL SIZE OF METER CAN. |
| | |
| | 15)NOTE:PLEASE VERIFY SIZE OF CONDUCTOR |
| | SHOWN FOR 30A COOKTOP. SHOWS #6 FOR THIS |
| | UNLESS SOME SORT OF ADAPTER IS USED, |
| | #6 WILL NOT FIT A 2P30A BRKR. |
| | PLEASE VERIFY. |
| | |
| | 16)NOTE: PLEASE SEE 210.52 FOR REQUIRED |
| | RECEPT SPACING IN HOUSE. THERE ARE A |
| | NUMBER OF MISSING RECEPTS. PLEASE SEE |
| | ONE SET OF PLANS HAS MOST OF THEM |
| | REDLINED, BUT EXACT LOCATIONS ARE NOT |
| | SPECIFIED. PLEASE ALSO SEE LEISURE "RM" |
| | RAILING AREA IS CONSIDERED "WALL SPACE" |
| | AND WILL REQUIRE RECEPTS PER 210.52. |
| | |
| | 17)NOTE: PLEASE SEE 210.52D, GFI RECEPT |
| | FOR BATHS ARE REQUIRED TO BE WITHIN |
| | 3' OF THE EDGE OF SINK. PLEASE SEE |
| | "HER" BATH AREA. |
| | |
| | 18)NOTE: PLEASE SEE FS 471, 481.FAC |
| | 61G15-23 |
| | PLEASE SEE PLANS THAT CONTAIN A TITLE |
| | BLOCK OF AN ARCH/ ENGINEERMUST BE |
| | SIGNED, DATED AND SEALED BY THAT |
| | ENGINEER/ OR ARCH. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO TWO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD MAY BE REQUIRED FOR |
| | REFERENCE BY SOME PLAN REVIEWERS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |