| 2004-07-06 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) THE ENGINEER IS REQUIRED TO SIGN AND |
| | SEAL THE PLAN SHEETS ON WHICH HIS TITLE |
| | BLOCK APPEARS. SEE FS 471. |
| | |
| | 3) FBC* 1804.2.2AREA OF QUESTIONABLE |
| | SOIL.SUBMIT A GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. |
| | |
| | 4) FBC 2405.2 REQUIRES WINDOWS WITHIN 3' |
| | HORIZONTALLY OF A TUB OR SHOWER TO HAVE |
| | SAFETY GLASS. SEE WINDOWS IN MASTER BATH |
| | |
| | 5) SPECIFY THE SIZE AND LOCATION OF THE |
| | ATTIC ACCESS ON THE SECOND FLOOR. SEE |
| | FBC 2309.6. |
| | |
| | 6) REVISE NOTE 11 ON SHEET 2. CITY |
| | AMENDMENTS TO FBC TABLE 2306.1 REQUIRES |
| | 8D RING-SHANK NAILS FOR ROOF SHEATHING |
| | IN ZONE 3 ON STRUCTURES WITH A MEAN ROOF |
| | HEIGHT OF 25'-35'. |
| | |
| | 7) PROVIDE A DOOR BUCK DETAIL. NOTE 13 |
| | ON SHEET 2 DOES NOT SPECIFY DOOR BUCKS. |
| | |
| | 8) SPECIFY THAT THE GUARDRAIL ON SHEET 3 |
| | MUST REJECT A 4" SPHERE PER FBC 1015.3. |
| | |
| | 9) FBC 1007.5 REQUIRES STAIRWAYS TO HAVE |
| | A HANDRAIL NOT LESS THAN 34" NOR MORE |
| | THAN 38" ABOVE THE LEADING EDGE OF A |
| | TREAD. SEE FBC 1007.5.3 FOR GRASPABILITY |
| | REQUIREMENTS. |
| | |
| | 10)SPECIFY THE REQUIRED DESIGN PRESSURES |
| | FOR THE WINDOWS ON SHEET 4. |
| | |
| | 11)SPECIFY THE R-VALUE OF THE INSULATION |
| | AT THE BLOCK WALLS. MUST CORRESPOND WITH |
| | THE ENERGY CALCS. |
| | |
| | 12) SPECIFY THE LOCATIONS AND MATERIALS |
| | USED FOR THE DRAFTSTOPPING AT THE FLOOR/ |
| | CEILING ASSEMBLY DIVIDING THE AREA INTO |
| | AREAS OF 500 SQFT OR LESS PER FBC 2305.2 |
| | AND 2305.2.6. |
| | |
| | 13) SPECIFY THE BOTTOM CORD LIVE LOAD ON |
| | THE PLANS. SEE FBC TABLE 1604.1. |
| | |
| | 14) SPECIFY THE CONNECTORS USED TO |
| | ATTACH THE BOTTOM CORD OF THE ROOF |
| | TRUSSES TO THE LEDGERS. |
| | |
| | 15) SPECIFY THE CONNECTORS FOR ATTACHING |
| | THE FLOOR TRUSSES TO THE LEDGERS. |
| | |
| | 16) SPECIFY THE FIREBLOCKING OF THE |
| | CONCEALED SPACES BETWEEN STRINGERS AT |
| | THE STAIRS AT THE TOP AND BOTTOM OF RUNS |
| | PER FBC 2305.1.4. |
| | |
| | 17) SPECIFY THE FIREBLOCKING OF THE |
| | FURRED SPACE AT THE EXTERIOR WALLS WHERE |
| | THEY MEET CEILINGS ON THE WALL SECTIONS |
| | PER FBC 2305.1.4. |
| | |
| | 18) SUBMIT DETAILS FOR FIREPLACE AND |
| | CHIMNEY. SPECIFICATIONS AND LISTING IF |
| | THEY ARE PREFAB. PROVIDE DETAILED |
| | DRAWINGS OF DIMENSIONS, MATERIALS, |
| | ATTACHMENTS, CONNECTORS, ETC. FOR FIRE- |
| | PLACE AND CHIMNEY. SPECIFY THE HEIGHT |
| | ABOVE ROOF FOR THE CHIMNEY AS PER FBC |
| | 2804. |
| | |
| | 19) FBC 1606.1.4 REQUIRES PROTECTION OF |
| | GLAZED OPENINGS. SUBMIT STORM PANEL |
| | PRODUCT APPROVAL, KEY PLAN AND INSTALLA- |
| | TION SCHEDULE OR PRODUCT APPROVALS FOR |
| | LARGE MISSLE IMPACT RESISTANT GLASS. |
| | |
| | 20) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE SAMPLE |
| | WITH NOAS. |
| | |
| | 21) SUBMIT STATE OR LOCAL PRODUCT |
| | APPROVALS FOR THE FOLLOWING: |
| | - ARCHED TOP WINDOWS (DESIGNER SHAPES) |
| | - ENTRY DOORS |
| | - SIDE SWING DOOR AT GARAGE |
| | - OVER HEAD GARAGE DOOR |
| | - STORM PANELS |
| | |