| Plan Review Notes For Permit 04060622 |
| Permit Number |
04060622 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-07-28 00:00:00 | *** REDLINED *** | | | | | | 1)NOTE: PLANS STILL SHOW 100A OCP FOR | | | 10HP MOTOR. | | | PLEASE SEE TABLE IN NEC 430 AND PLEASE | | | SEE OCP 125% OF MOTOR LOAD WHICH IS | | | SHOWN AS 50A'S IN NEC TABLE. | | | THIS WILL NEED TO BE CORRECTED IN FIELD. |
|