| Plan Review Notes For Permit 04060622 |
| Permit Number |
04060622 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-16 00:00:00 | ************* UNSAT ********** | | | | | | 1)NOTE: PLEASE CORRELATE CONDUCTORS ON | | | RISER DIAGRAM. | | | SERVICE IS SHOWN AS 3/PHASE. | | | PLEASE SEE 250.6,250.24 | | | SEC'S WOULD CONTAIN NEUTRAL TO FIRST | | | MEANS OF DISCONNECT. | | | 215.5 | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|