2004-11-09 00:00:00COMMENTS AND NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED.
  
 1) FIRE DEPARTMENT REQUIRES 20 FEET WIDE
 MINIMUM OPENING FOR ACCESS.
  
 2) IS THERE A KNOX-KEY OPERATED CONTROL
 GATE.
  
 3) THIS GATE OPERATION HAVE TO BE FAIL
 SAFE POWERED.
  
 4) CUT SHEETS AND SPEC'S ON THE GATES
 CONTROLS AND EQUIPMENT.
  
 5) SEPARATE PLANS AND PERMIT APPLICATION
 MAYBE REQUIRED FOR THE GATE AND
 CONTROLS.
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722