Plan Review Notes
Plan Review Notes For Permit 04060620
Permit Number 04060620
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-07-13 00:00:00*********DENIED*************************
 1) ENTRY GATE SHOWS 14 FEET WIDE SWING
 OPENING. FIRE DEPARTMENT REQUIRES 20
 FEET WIDE MINIMUM OPENING FOR ACCESS.
 OR DOES BOTH GATES OPEN MAKING IT 28
 FEET OPENING.
  
 2) HOW WILL FIRE DEPT GAIN ACCESS THRU
 THE SECURITY GATES, IS THERE KNOX-BOX
 KEY OPERATED CONTROL.
  
 3) WILL THESE GATES BE FAIL SAFE POWERED
  
 4) SEPARATE PLANS AND PERMIT APPLICATION
 MAYBE REQUIRED WITH CUT SHEETS ON THE
 GATES CONTROLS AND EQUIPMENT.
  
 NATE MCCRAY, CAPTAIN
 835-2910 OR 805-6722