1 |
|
| Notes |
| Date |
Text |
| 2004-07-07 00:00:00 | PROVISO: | | | PER THE REVISED 2001 FBC(M) 601.4 | | | EXCEPTION #1 & 3: | | | #1) RETURN TRANSFER DUCTS SHALL BE | | | INCREASED 1 1/2 TIMES THE SQUARE INCHES | | | OF THE SUPPLY AIR TO THAT SPACE. | | | EXAMPLE:7" SUPPLY SHALL HAVE A 9" R/A | | | 9" SUPPLY SHALL HAVE A 12 R/A | | | SEE THE ATTACHED SCHEDULE FOR FUTURE | | | SIZING. | | | #3) ALL SUPPLY AIR INTO A MASTER SUITE | | | IS TO BE INCLUDED FOR A "TOTAL" SUPPLY | | | AIR TO THE SUITE (INCLUDE BATHROOM, | | | CLOSET, ETC).R/A IS TO BE CALCULATED | | | BASED ON THE TOTAL SUPPLY AIR TO A | | | MASTER SUITE. | | | | | | PLEASE REVISE R/A DUCTS ACCORDINGLY. | | | | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|