| Plan Review Notes For Permit 04060563 |
| Permit Number |
04060563 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-16 00:00:00 | *************DENIED********************* | | | 1) WHAT ARE THE WALLS AND CEILINGS | | | INTERIOR FINISH CLASSIFICATION? CLASS "A | | | "B" OR "C". | | | | | | 2) IT APPEARS THAT ADDITIONAL EXIT SIGN | | | AND EMERGENCY LIGHT ARE NEEDED FOR THE | | | CORRIDOR LEADING FROM OFFICE #4 TO THE | | | RECEPTION AREA. | | | | | | 3) WILL THESE ALTERATIONS AFFECT FIRE | | | SPRINKLER COVERAGE AND FIRE ALARM SYSTEM | | | | | | 4) SEPARATE PLANS AND PERMIT APPLICATION | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM SYSTEM REMODEL. | | | | | | NATE MCCRAY, CAPTAIN | | | 835-2910 OR 805-6722 |
|