| Plan Review Notes For Permit 04060563 |
| Permit Number |
04060563 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-15 00:00:00 | LOAD CALCULATION TO ALSO BE DONE ON | | | SERVICE. | | | | | | LOAD CALCULATIONS IS OK BUT WHEN THE | | | NUMBER OF OUTLETS IS KNOWN THEN 180 VA | | | EACH IS USED THEN 220.13 | | | | | | RISER SHOWS EAST PANEL TO BE 100A FED | | | BY 200A MAIN! | | | | | | AHU CLOSET ON WEST SIDE NEEDS LIGHT AND | | | OUTLET. | | | | | | NEDD TO SHOW BRASNCH CIRCUIT NUMBERS ON | | | THE PLANS FOR THE OUTLETS AND LIGHTS. | | | | | | PANEL SCHEDULES ARE IDENTICAL SPACES | | | ARE OT!!!!! | | | | | | PAGE E-2 SHOW A SATELITE OUTLET OUTSIDE! | | | | | | ANY QUESTIONS CALL JAKE LEAHY 805-6740 |
|