| 2004-06-18 00:00:00 | PROVISO: | | | TRANSFER GRILLE FROM BEDROOM WITH 300 | | | CFM OF SUPPLY AIR, PER THE REVISED 2001 | | | FBC(M) 601.4 EXCEPTION #2 - TRANSFER | | | GRILLES SHALL USE 50 SQ IN OF GRILLE | | | AREA TO 100 CFM OF SUPPLY AIR.PLEASE | | | SIZE TRANSFER GRILLE ACCORDINGLY. | | | | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|