| Plan Review Notes For Permit 04060548 |
| Permit Number |
04060548 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-28 00:00:00 | DENIED; | | | 1.SEE ELECTRICAL PLAN REVIEW NOTE #6 | | | ARCHITECT TITAL BLOCK. | | | 2.PAGE P-2. MASTER BATH AND 1/2 BATH. | | | HORIZONTAL DRY VENTS NOT PERMITED ( 3" | | | MASTER BATH ). | | | 3.SHOWER AND TUB NOT VENTED AND ONE W/C. | | | SEE TABLE 906.1 MAXIMUM DISTANCE OF | | | TRAP TO VENT. | | | 4.W/M DISCHARGE IS 2" MIN. AND MIN. DIA. | | | PIPE UNDER SLAB IS 2". | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|