| Plan Review Notes For Permit 04060548 |
| Permit Number |
04060548 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-15 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE GROUNDING ELECTRODE CONDUCTOR | | | CONDUCTOR IS UNDERSIZED PER 250.66. | | | SHOULD BE #1/0 FOR 400 AMP SERVICE (400 | | | MCM). | | | | | | 2} THE GRC MUST COMPLY WITH 250.50 REF | | | 250.52.( FOOTER STEEL). | | | | | | 3} APPLIANCE CIRCUIT #15 INCORRECTLY | | | LISTS A 3 KVA LOAD ON A SINGLE POLE 20 | | | AMP BREAKER & THE #12 WIRE. | | | | | | 4} A SMOKE DETECTOR IS REQUIRED BY THE | | | STAIRWELL ON THE FIRST FLOOR TO COMPLY | | | WITH 905.2.2 FBC. | | | | | | 5} RECEPTACLES ARE REQUIRED TO BE ADDED | | | IN THE MASTER SUITE #2 AND BEDROOM #3 TO | | | COMPLY WITH 210.52(A)(2)(1). 2'OR MORE | | | | | | 6} THE ARCHITECTS TITLE BLOCK MUST | | | CONTAIN ALL THE INFORMATION REQUIRED BY | | | FAC. 61G1-16.004. SEE (2), FIRM LICENSE | | | NUMBER. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|