2004-07-06 00:00:00PROVISO:
 PLANS DO NOT INDICATE RETURN AIR.PER
 2001 FBC(M) 601.4, ROOMS THAT ARE
 SEPARATED BY DOORS FROM THE RETURN AIR,
 SHALL HAVE A RETURN AIR JUMPER, TRANSFER
 OR DUCTED RETURN FROM THAT SPACE.
  