Plan Review Notes
Plan Review Notes For Permit 04060487
Permit Number 04060487
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-15 00:00:00************* UNSAT ******************
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A SUBMITTED
 PANEL SCHEDULE. PLEASE SHOW NEW AND
 OR EXSITNG TIE-INS FOR CIRCUITS.
 215.5
  
 2)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 3)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 ON TITLE BLOCK. THIS IS TO INCLUDE THE
 REQUIRED CERTIFICATE OF AUTHORIZATION
 PER FS 481.219.
 FAC 61G1-16.004
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 OR NOT COMMENT IS MADE FROM OTHER REVIEW
 -ERS.
  
 4)NOTE: PLEASE SEE 2002 NEC FOR ARC
 FAULT PROTECTION FOR NEW CIRCUITING TO
 BEDRMS. 210.12
  
 PLEASE SEE COMMENT S FROM OTHER REVIEWER
 -S WHICH MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  