Plan Review Notes
Plan Review Notes For Permit 04060444
Permit Number 04060444
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-14 00:00:00**************** UNSAT ************
  
 1)NOTE: PLEASE SEE FS 481.219, FAC 61G1-
 16.004. PLEASE INCLUDE LICENSE #S'
 FOR COMPANY/FIRM. M"SBA".
  
 2)NOTE: PLEASE SEE PLANS ARE MISSING
 MIN REQUIRED FOR UNITS.
 PANEL SCHEDULES?
 CIRCUITING ON PLANS AND CORRELATE WITH
 SUBMITTED PANEL SCHEDULES TO BE SUBMITT-
 -ED.
  
 3)NOTE: PLEASE SEE 600.5 FOR MIN SIGN
 CIRCUIT(S).
  
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO
 METERBANK. 250.122
  
 5)NOTE: PLEASE PROVIDE INFORMATION FOR
 NEW SERVICE/METERBANK MAINS. FEEDS TO
 PANELS.215.5/250
 PLEASE PROVIDE LETTER FROM FPL PERMITT-
 -ING METERBANK TO BE ON THE LOAD SIDE
 OF NEW MAIN WITHOUT ANY CT OR FPL
 MEASURING DEVICE ON LINE-SIDE OF MAIN
 DISCONNECT.
  
 6)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR EXIT/EM LTS. PLEASE SEE 700.12E FOR
 CIRCUITING.
  
 7)NOTE: PLEASE SEE PERMIT APPLICATION,
 NEEDS TO CORRELATE WITH PLANS SUBMITTED
 FOR SCOPE OF WORK.
  
 8)NOTE: PLEASE SEE FBC 104.6.5 FOR
 VALUE TO INCLUDE ALL LABOR AND MATERIALS
 PLEASE SEE BLDG VALUATION.
  
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD PLANS MAY BE SUBMITTED
 FOR REFERENCE ONLY. THIS MAY BE REQUIRED
 OF SOME REVIEWERS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]