2004-07-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04060444
 ADD: 534 DATURA ST
 CONT: TAYCON CONSTRUCTION
 TEL: (561)622-2699
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) "FIRE DISTRICT" 609.2.1 NO TYPE VI
 CONSTRUCTION ON EXTERIOR WALLS. INFILL
 WALLS AT OLD DOORWAYS.
  
 3) LEASE SPACE, E-1 DOES NOT PROVIDE
 EXIT LIGHTING FOR LEASE SPACE NOR FOR
 BAY# 2.
  
 4)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 A) MISSING THE PRODUCT TESTING REPORTS
 FOR SIMPSON AND USP PRODUCTS.
 B) MISSING HOLLOW METAL DOOR
 C) SITE SPECIFIC ENGINEERING.
 1)) INFORMATION ON THE SITE SPECIFIC
 FORM 1-5 HAS TO DO WITH THE MANUFACTURER
 NOT THE JOBSITE.
 2)) #7 NAME OF APPROVED THIRD PARTY
 QUALITY ASSURANCE ENTITY NOT COMPLETE,
 IF THE DESIGNER OF RECORD TO BE THE
 QUALITY ASSURANCE ENTITY, TO GO TO THE
 MANUFACTURING PLANT VERIFY PRODUCTION.
 THEN INSPECT THE ASSEMBLIES AT INSTALA-
 TION. PRODUCE AN AFFIDAVIT.
 3)) THE SITE SPECIFIC ENGINEERING DOES
 NOT PROVIDE ANY INFORMATION AS TO THE
 STRENGTH OF GLAZING.
 4)) 3401.7.2.4. PROVIDE INFORMATION ON
 THE LARGE MISSLE IMPACT PROTECTION
 REQUIRED BY CHAPTER 1606.6.SEE GLAZING
 NOTE ON A-5.
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 5)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 6) SHEET A-5 INDICATES THE USE OF A
 1-HR WALL, WITH A U. L. LISTING OF 401,
 THERE IS NO SUCH LISTING, THERE IS A
 U401,OR V401?
  
 7) SHEET A-5 SECTIONS 8 & 9 INDICATE
 WOOD INFILL BUT NO MENTION AS TO THE
 ATTACHMENT OT THE SUBSTRATA.
  
 8) SITE SPECIFIC ENGINEERING SUBMITTED
 SEE SHEET 12 (TABLE 1606.2B) IS TO BE
 USED WITH BUILDINGS WITH A ROOF HEIGTH
 OF 30' OR LESS, SEE TABLE 1606.2D FOR
 BUILDINGS OVER 30' WITH ASSOCIATED
 MULTIPLIER, BUILDINGS 55'= 1.19. RE-
 EVALUATE SUBMITTED CALCULATIONS!
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026