| Plan Review Notes For Permit 04060406 |
| Permit Number |
04060406 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A0.1 ACCESSIBLE DETIAL FOR SINK | | | SHALL SHOW KNEE CLEARANCE 11-4.24.3, | | | DEPTH OF SINK 11-4.24.4, EXPOSED PIPES & | | | SURFACES 11-4.24.6. | | | 2) SHT A0.2 ALL CAPPED AND DEMO'D PLUMB- | | | ING PIPES SHALL BE INSPECTED PRIOR TO | | | COVERING. SECTION 104.2.1 | | | 3) SHT A1.0 SHOW CLEAR FLOOR SPACE FOR | | | SINK IN ROOM 521. 11-4.24.5. | | | 4) SHT A1.0 SHOW CLEAR FLOOR SPACE FOR | | | ACCESSIBLE DRINKING FOUNTAIN. 11-4.15.5 | | | 5) SHT A1.1 SHOW CLEAR FLOOR SPACE FOR | | | SINK IN ROOM 643. 11-4.24.5 | | | 6) SHT A1.1 SHOW CLEAR FLOOR SPACE FOR | | | ACCESSIBLE DRINKING FOUNTAIN. 11-4.15.5 | | | 7) SHT A2.0 BREAK ROOM/STORAGE ELEVATION | | | MAXIMUM 34" TO SINK. 11-4.24.2 | | | 8) SHT P.2 5TH & 6TH FLOOR WATER RISER | | | DIAGRAMS ARE MISLABELED AS SANITARY | | | RISERS. - WATER HAMMER ARRESTORS SHALL | | | BE LOCATED NEAR THE FIXTURES, NOT IN THE | | | CEILING AS SHOWN. PDI-WH 201 AND MANUF. | | | INSTALLATION INSTRUCTIONS. SECTION 604.9 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|