Plan Review Notes
Plan Review Notes For Permit 04060367
Permit Number 04060367
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-17 00:00:001. NEED RISER SHOWING WIRE SIZES.
  
 2. PANEL SCHEDULE DOES NOT SHOW BATH
 CIRCUIT(S).
  
 3. PANEL SCHEDULE DOES NOT SHOW ARCFAULT
 BREAKERS.
  
 4. SMOKE DETECTORS NEED TO BE SHOWN AND
 THEY NEED TO BE 3' FROM THE BATH AND
 KITCHEN.