| Plan Review Notes For Permit 04060364 |
| Permit Number |
04060364 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-24 00:00:00 | DENIED | | | 1.DOOR FROM CLASS ROOM 1 TO CORRIDOR | | | 1 NEEDS 18" CLEAR AT LATCH SIDE OF DOOR. | | | | | | 2.OFFICE 5 WILL NEED CLEAR ACCESS. | | | | | | 3.SHOW LIFE SAFTEY PLAN, SHOW | | | DIRECTION OF EGRESS AND ILLUMINATION | | | THROUGH VESTIBULE TO CORRIDOR #2. | | | FBC 1016 | | | | | | 4.CONFERENCE ROOM COUNTERTOP AT | | | SINK AREA TO BE 34" HIGH FBC 11-4.24.2 | | | | | | ANY QUESTIONS CALL ME | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|