| Plan Review Notes For Permit 04060361 |
| Permit Number |
04060361 |
|
| Review Stop |
P |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2005-03-26 00:00:00 | GAS REVISION DENIED | | | | | | 1) GAS RISER DIAGRAM MEASURMENTS FOR GAS | | | LEG #1 ARE NOT ALL SHOWN. SEE | | | HIGHLIGHTED SECTIONS AND INDICATE THE | | | LENGHT FOR EACH SECTION. THERE IS | | | CONFUSION ON THE MEASURMENT 18'@ 2". | | | PLEASE INDICATE WHICH SECTION OF PIPE | | | THIS MEASURMENT IS FOR, THEN SHOW THE | | | MEASUREMENT FOR THE OTHER SECTION OF | | | PIPE. SECTION 104.2.1. | | | 2) ADDING UP THE AVAILABLE MEASURMENTS | | | FOR GAS LEG #1, THE TOTAL DEVELOPED | | | LENGTH OF THAT LEG IS MORE THAN THE 89' | | | INDICATED. PLEASE RECALCULATE THE | | | DEVELOPED LENGTH AFTER ADDING ADDITIONAL | | | PIPE LENGHTS ON ISOMETRIC. IF OVER 100' | | | THAN 2-1/2" PIPE WILL BE REQUIRED. SEE | | | TABLE 402(2) FUEL GAS CODE. | | | 3) NO MANUF. SPECIFICATION SHEET FOR THE | | | WATER HEATER HAS BEEN SUBMITTED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|