| Plan Review Notes For Permit 04060361 |
| Permit Number |
04060361 |
|
| Review Stop |
P |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2005-03-15 00:00:00 | REVISION/DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | A) THE FOLLOWING INFORMATION IS REQUIRED | | | FOR THE GAS REVISION. | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. - MANY CUT SECTIONS DO | | | NOT SHOW THE LENGTH REQUIRED. | | | | | | 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 - NEW | | | GAS FIXTURES NOT SHOWN ON PREVIOUS | | | REVIEWS ARE "CHAR GRILLE", AND "STOCK | | | POT RANGE". SUBMIT MANUF. SPECIFICATION | | | SHEETS SHOWING BTU'S AND LISTING BY AN | | | APPROVED TESTING AGENCY. - RANGE ON | | | PREVIOUS REVIEW AND MANUF. SHEET | | | INDICATED 230,000 BUT. REVISION SHOWS | | | 110,000 BTU. PLEASE CLARIFY, AND IF | | | DIFFERENT APPLIANCES NEW SHEETS WILL BE | | | REQUIRED. - STEAM TABLE SHOWS 15,000 BTU | | | PREVIOUS SHOWED 27,500 BTU. PLEASE | | | CLARIFY AND IF DIFFERENT APPLIANCES NEW | | | SHEETS WILL BE REQUIRED. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | | | | |
|