2005-01-11 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) MEP SHEETS HAVE TWO DIFFERENT
 SIGNATURES FOR THE SAME PE. PLEASE HAVE
 ENGINEER SIGN WITH LEGAL SIGNATURE. FAC
 61G15-23.002 & FS 471.025
 2) SHT MEP-9 INDICATES "GAS RUN UNDER
 SLAB (SEE DETAIL)" IN TWO LOCATIONS. NO
 DETAIL FOR THIS IS SHOWN. PLEASE
 INDICATE WHERE THE DETAIL CAN BE
 LOCATED. - REQUIRED INSTALLATION WILL BE
 TO HAVE THE SLAB CUT OUT AND GALV. PIPE
 RUN IN SLAB, PAINTED WITH BITUMINOUS
 PAINT, THEN LIGHT WEIGHT CONCRETE POURED
 OVER THE PIPE AFTER TESTING AND APPROVAL
 BY INSPECTOR.
  
  