2004-12-27 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS STILL SHOWN FROM
 METER TO MAIN (FIRST MEANS OF DISC).
 PLEASE SEE 250.6,250.24. NO EQUIPMENT
 GRND UNTIL AFTER THE FIRST MEANS OF
 DISC.
  
 2)NOTE: PLEASE SEE MEP PLANS HAVE TWO
 DIFFERENT SIGNATURES FOR THE SAME PE.
 PLEASE HAVE ENGINEER SIGN WITH LEGAL
 SIGNATURE AS ON FILE.
 FS 471.025
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  