| 2004-09-22 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | |
| | A) FOLLOWING COMMENTS FROM THE FIRST RE- |
| | VIEW HAVE NOT BEEN ADDRESSED. THE COMME- |
| | NT NUMBER FROM THE FIRST REVIEW WILL BE |
| | USED TO AVOID CONFUSION. |
| | 1) ROUTE PLANS TO DBPR HOTEL AND RESTUR- |
| | ANT DIVISION FOR REVIEW. PLANS SHALL BE |
| | STAMPED AND WORK SHEETS ATTACHED TO EACH |
| | SET OF PLANS FOR REVIEW WHEN RESUBMITT- |
| | ING TO CITY WPB FOR REVIEW. SECTION 101. |
| | 4.7 |
| | 2) SHT A-2 PRIVATE TOILET ROOM SHALL BE |
| | ADAPTABLE. SHOW TURNING AREA IN ROOM AND |
| | INDICATE TOILET TO BE 18" OFF WALL TO |
| | THE CENTER OF THE FIXTURE. SECTION 11-4. |
| | 1.3(11) |
| | 4) SHT A-4 SUBMIT CALCULATIONS FOR PRIM- |
| | ARY AND SECONDARY ROOF DRAINS PER SECT- |
| | IONS 1106, & 1107. SHOW SQUARE FOOTAGE |
| | OF EACH ROOF SECTION BEING DRAINED. SHOW |
| | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS BEING ADDED TO S.F. OF ROOF |
| | AREAS. INDICATE SIZE OF GUTTER. SHOW THE |
| | HIGH POINTS OF THE GUTTERS. TABLE 1106.6 |
| | 5) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE FOR SIZING OF GREASE INTER- |
| | CEPTOR. WASTE ORD 2938-96 @ (561) 837- |
| | 4074. - SUBMIT REQUIREMENT SHEET |
| | 8) SUBMIT A WATER RISER DIAGRAM IN ISO- |
| | METRIC FORM AS REQUIRED BY SEC 104.3.1.1 |
| | 9) SUBMIT A STORM RISER DIAGRAM. SHOW |
| | TERMINATION OF STORM PIPING. SECTION |
| | 104.3.1.1 |
| | 10) GAS REQUIREMENTS |
| | B) SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED. |
| | F) SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR PER FBC-2001 FUEL GAS CODE SECTION |
| | 304 - WATER HEATER ROOM REQUIRES COMBUS- |
| | TION AIR. |
| | H) SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE, AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | I) SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH THE |
| | STANDARDS NFPA 54, AND THE FBC-2001 FUEL |
| | GAS CODE SECTION 402.2 |
| | 11) AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE. UTILITY ORD./SECTION 608. |
| | 13.2. |
| | **************NEW COMMENTS************** |
| | 1B) SHT A-2 STAFF TOILET ROOM REQUIRES |
| | MINIMUM 5"3" WIDE TO ACCOUNT FOR 18" TO |
| | CENTER OF W/C OFF WALL, 30" CENTER OF |
| | W/C TO LAV, AND 15" OFF WALL TO CENTER |
| | OF LAV. SECTION 405.3.1 |
| | 2B) SHT MEP9 GREASE WASTE RISER DIAGRAM. |
| | FLOOR DRAIN SHALL NOT SAFEWASTE INTO THE |
| | FLOOR SINK, BUT SHALL TIE INTO THE VENT- |
| | ED LINE SEPARATELY. (TAKE 0UT KITCHEN) |
| | ALSO MAXIMUM DISTANCE FROM VENT TO TRAP |
| | IS 6 FEET. TABLE 906.1 |
| | 3B) SHT MEP9 TAKE OUT DRIVE THRU, FLOOR |
| | DRAIN IS NOT AN APPROVED INDIRECT WASTE |
| | RECEPTOR. USE A FLOOR SINK OR A HUB |
| | DRAIN PER SECTION 802.3 OR 802.3.2. |
| | 4B) SHT MEP9 GAS RISER DIAGRAM AND GAS |
| | LOAD CALCULATIONS DO NOT REFLECT EACH |
| | OTHER. BOILER @ 150,000 BTU & FRYER @ |
| | 98,000 BTU ARE NOT SHOWN ON RISER DIAGR- |
| | AM. PLEASE CLAIRFY/CORRELATE. SECTION |
| | 104.2.1. |
| | ********WHEN RESUBMITTING PLANS********* |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |