Plan Review Notes
Plan Review Notes For Permit 04060361
Permit Number 04060361
Review Stop P
Sequence Number 2
Notes
Date Text
2004-09-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 A) FOLLOWING COMMENTS FROM THE FIRST RE-
 VIEW HAVE NOT BEEN ADDRESSED. THE COMME-
 NT NUMBER FROM THE FIRST REVIEW WILL BE
 USED TO AVOID CONFUSION.
 1) ROUTE PLANS TO DBPR HOTEL AND RESTUR-
 ANT DIVISION FOR REVIEW. PLANS SHALL BE
 STAMPED AND WORK SHEETS ATTACHED TO EACH
 SET OF PLANS FOR REVIEW WHEN RESUBMITT-
 ING TO CITY WPB FOR REVIEW. SECTION 101.
 4.7
 2) SHT A-2 PRIVATE TOILET ROOM SHALL BE
 ADAPTABLE. SHOW TURNING AREA IN ROOM AND
 INDICATE TOILET TO BE 18" OFF WALL TO
 THE CENTER OF THE FIXTURE. SECTION 11-4.
 1.3(11)
 4) SHT A-4 SUBMIT CALCULATIONS FOR PRIM-
 ARY AND SECONDARY ROOF DRAINS PER SECT-
 IONS 1106, & 1107. SHOW SQUARE FOOTAGE
 OF EACH ROOF SECTION BEING DRAINED. SHOW
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS BEING ADDED TO S.F. OF ROOF
 AREAS. INDICATE SIZE OF GUTTER. SHOW THE
 HIGH POINTS OF THE GUTTERS. TABLE 1106.6
 5) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF GREASE INTER-
 CEPTOR. WASTE ORD 2938-96 @ (561) 837-
 4074. - SUBMIT REQUIREMENT SHEET
 8) SUBMIT A WATER RISER DIAGRAM IN ISO-
 METRIC FORM AS REQUIRED BY SEC 104.3.1.1
 9) SUBMIT A STORM RISER DIAGRAM. SHOW
 TERMINATION OF STORM PIPING. SECTION
 104.3.1.1
 10) GAS REQUIREMENTS
 B) SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED.
 F) SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER FBC-2001 FUEL GAS CODE SECTION
 304 - WATER HEATER ROOM REQUIRES COMBUS-
 TION AIR.
 H) SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE, AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 I) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH THE
 STANDARDS NFPA 54, AND THE FBC-2001 FUEL
 GAS CODE SECTION 402.2
 11) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. UTILITY ORD./SECTION 608.
 13.2.
 **************NEW COMMENTS**************
 1B) SHT A-2 STAFF TOILET ROOM REQUIRES
 MINIMUM 5"3" WIDE TO ACCOUNT FOR 18" TO
 CENTER OF W/C OFF WALL, 30" CENTER OF
 W/C TO LAV, AND 15" OFF WALL TO CENTER
 OF LAV. SECTION 405.3.1
 2B) SHT MEP9 GREASE WASTE RISER DIAGRAM.
 FLOOR DRAIN SHALL NOT SAFEWASTE INTO THE
 FLOOR SINK, BUT SHALL TIE INTO THE VENT-
 ED LINE SEPARATELY. (TAKE 0UT KITCHEN)
 ALSO MAXIMUM DISTANCE FROM VENT TO TRAP
 IS 6 FEET. TABLE 906.1
 3B) SHT MEP9 TAKE OUT DRIVE THRU, FLOOR
 DRAIN IS NOT AN APPROVED INDIRECT WASTE
 RECEPTOR. USE A FLOOR SINK OR A HUB
 DRAIN PER SECTION 802.3 OR 802.3.2.
 4B) SHT MEP9 GAS RISER DIAGRAM AND GAS
 LOAD CALCULATIONS DO NOT REFLECT EACH
 OTHER. BOILER @ 150,000 BTU & FRYER @
 98,000 BTU ARE NOT SHOWN ON RISER DIAGR-
 AM. PLEASE CLAIRFY/CORRELATE. SECTION
 104.2.1.
 ********WHEN RESUBMITTING PLANS*********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS