Plan Review Notes
Plan Review Notes For Permit 04060361
Permit Number 04060361
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2004-09-16 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. A MINUMUM OF AT
 LEAST 6" HIGH NUMBERS ARE REQUIRED.
  
 2) AN ILLUMINATED EXIT SIGN REQUIRED
 AT MAIN DOOR LEADING TO PATIO AREA.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD,DUCT, AND SUPPRESSION SYSTEM.
  
 4) AN OCCUPANT LOAD SIGN SHALL BE
 POSTED INDICATING 80 OCCUPANTS ONLY
 SINCE THE BUILDING IS NOT PLANNED TO
 BE FIRE SPRINKLER PROTECTED.
  
 5) COULD NOT LOCATE A DOOR SCHEDULE
 WITH THE PLANS.
  
 6) NO PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS OR GUARDRAILS COULD
 BE LOCATED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910