| 2004-07-17 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) ROUTE PLANS TO DBPR HOTEL AND RESTUR- |
| | AND DIVISION FOR REVIEW. PLANS SHALL BE |
| | STAMPED AND WORK SHEET ATTACHED TO EACH |
| | SET OF PLANS FOR REVIEW WHEN RESUBMITT- |
| | ING TO CITY WPB FOR REVIEW. |
| | 2) SHT A-2 PRIVATE TOILET ROOM SHALL BE |
| | ADAPTABLE. INDICATE BACKING FOR GRAB |
| | BARS, SHOW TURING AREA IN ROOM AND IN- |
| | DICATE TOILET TO BE 18" OFF WALL. SECT- |
| | ION 11-4.1.3(11). |
| | 3) SHT A-2 STAFF TOILET ROOM SHALL BE |
| | ACCESSIBLE. SECTION 11-4.1.3(11). SUBMIT |
| | A DETAIL SHOWING COMPLIANCE WITH SECT- |
| | IONS 11-4.16, 11-4.19, & 11.4.22 AND ALL |
| | SUBSECTIONS. |
| | 4) SHT A-4 SUBMIT CALCULATIONS FOR PRIM- |
| | ARY AND SECONDARY ROOF DRAINS PER SECT- |
| | IONS 1106, & 1107. SHOW SQUARE FOOTAGE |
| | OF EACH ROOF SECTION BEING DRAINED. SHOW |
| | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS BEING ADDED TO SF OF ROOF. SHOW |
| | ALL AREAS OF ROOFS DRAINING ONTO THE |
| | ROOF FROM ABOVE ADDED TO ROOF SF. - IN- |
| | DICATE SIZE AND SLOPE OF GUTTER. SHOW |
| | HIGH POINT OF GUTTER. SHOW SIZE OF DOWN- |
| | SPOUTS. SEE TABLE 1106.6. - PLEASE INDI- |
| | CATE HOW THE ROOF OVER THE SMOKER ROOM |
| | IS BEING DRAINED. GUTTERS AND DOWNSPOUTS |
| | ARE REQUIRED ON ALL BUILDINGS WITH EAVES |
| | OF LESS THAN 6" HORIZONTAL PROJECTION |
| | EXCEPT FOR GABLE END RAKES. SECTION |
| | 1503.4.4 |
| | 5) CONTACT RODNEY COMPO ENVIRONMENTAL |
| | COMPLIANCE FOR SIZING OF GREASE INTER- |
| | CEPTOR. WASTE ORD #2938-96 @ (561) 837- |
| | 4074. |
| | 6) SHT A-7 ROOM ELEVATION SHOWS ACCESS- |
| | IBLE URINAL ON RIGHT SIDE, BUT FLOOR |
| | PLAN SHOWS CLEAR FLOOR SPACE FOR URINAL |
| | ON THE LEFT SIDE. PLEASE CORRELATE FLOOR |
| | PLAN AND ELEVATION DETAIL. SEC 104.2.1. |
| | 7) SHT MEP-4 ICE MAKER DOES NOT SHOW A |
| | FLOOR SINK OR HUB DRAIN FOR DRAINING |
| | FIXTURE. PLEASE CLARIFY. SECTION 301.3 |
| | 8) A SANITARY AND A WATER RISER DIAGRAM |
| | IN ISOMETRIC FORM ARE REQUIRED PER SEC |
| | 104.3.1.1 |
| | 9) SUBMIT A STORM RISER DIAGRAM AND A |
| | SECONDARY DRAIN STORM RISER DIAGRAM. |
| | SECTION 104.3.1.1 |
| | 10) THE FOLLOWING INFORMATION IS REQUIR- |
| | ED FOR REQUIRED GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | H. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | J. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | K. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | L. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | 11) AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE. UTILITY ORD/SEC 608.13.2. |
| | 12) THE FIRM LICENSE NUMBER AND PRINTED |
| | NAME OF THE ARCHITECT SHALL APPEAR ON |
| | THE TITLE BLOCK ON EACH SHEET SIGNED/ |
| | SEALED/DATED BY ARCHITECT OF RECORD. |
| | FAC 61G1-16.004(2)(5) & FS 481.2055. |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) - FS 471.025 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |