Plan Review Notes
Plan Review Notes For Permit 04060361
Permit Number 04060361
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ROUTE PLANS TO DBPR HOTEL AND RESTUR-
 AND DIVISION FOR REVIEW. PLANS SHALL BE
 STAMPED AND WORK SHEET ATTACHED TO EACH
 SET OF PLANS FOR REVIEW WHEN RESUBMITT-
 ING TO CITY WPB FOR REVIEW.
 2) SHT A-2 PRIVATE TOILET ROOM SHALL BE
 ADAPTABLE. INDICATE BACKING FOR GRAB
 BARS, SHOW TURING AREA IN ROOM AND IN-
 DICATE TOILET TO BE 18" OFF WALL. SECT-
 ION 11-4.1.3(11).
 3) SHT A-2 STAFF TOILET ROOM SHALL BE
 ACCESSIBLE. SECTION 11-4.1.3(11). SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH SECT-
 IONS 11-4.16, 11-4.19, & 11.4.22 AND ALL
 SUBSECTIONS.
 4) SHT A-4 SUBMIT CALCULATIONS FOR PRIM-
 ARY AND SECONDARY ROOF DRAINS PER SECT-
 IONS 1106, & 1107. SHOW SQUARE FOOTAGE
 OF EACH ROOF SECTION BEING DRAINED. SHOW
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS BEING ADDED TO SF OF ROOF. SHOW
 ALL AREAS OF ROOFS DRAINING ONTO THE
 ROOF FROM ABOVE ADDED TO ROOF SF. - IN-
 DICATE SIZE AND SLOPE OF GUTTER. SHOW
 HIGH POINT OF GUTTER. SHOW SIZE OF DOWN-
 SPOUTS. SEE TABLE 1106.6. - PLEASE INDI-
 CATE HOW THE ROOF OVER THE SMOKER ROOM
 IS BEING DRAINED. GUTTERS AND DOWNSPOUTS
 ARE REQUIRED ON ALL BUILDINGS WITH EAVES
 OF LESS THAN 6" HORIZONTAL PROJECTION
 EXCEPT FOR GABLE END RAKES. SECTION
 1503.4.4
 5) CONTACT RODNEY COMPO ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF GREASE INTER-
 CEPTOR. WASTE ORD #2938-96 @ (561) 837-
 4074.
 6) SHT A-7 ROOM ELEVATION SHOWS ACCESS-
 IBLE URINAL ON RIGHT SIDE, BUT FLOOR
 PLAN SHOWS CLEAR FLOOR SPACE FOR URINAL
 ON THE LEFT SIDE. PLEASE CORRELATE FLOOR
 PLAN AND ELEVATION DETAIL. SEC 104.2.1.
 7) SHT MEP-4 ICE MAKER DOES NOT SHOW A
 FLOOR SINK OR HUB DRAIN FOR DRAINING
 FIXTURE. PLEASE CLARIFY. SECTION 301.3
 8) A SANITARY AND A WATER RISER DIAGRAM
 IN ISOMETRIC FORM ARE REQUIRED PER SEC
 104.3.1.1
 9) SUBMIT A STORM RISER DIAGRAM AND A
 SECONDARY DRAIN STORM RISER DIAGRAM.
 SECTION 104.3.1.1
 10) THE FOLLOWING INFORMATION IS REQUIR-
 ED FOR REQUIRED GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 11) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. UTILITY ORD/SEC 608.13.2.
 12) THE FIRM LICENSE NUMBER AND PRINTED
 NAME OF THE ARCHITECT SHALL APPEAR ON
 THE TITLE BLOCK ON EACH SHEET SIGNED/
 SEALED/DATED BY ARCHITECT OF RECORD.
 FAC 61G1-16.004(2)(5) & FS 481.2055.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS