| 2004-06-22 00:00:00 | DENIED: |
| | 1.SEE COMMENT #1 BY DEWEY PALMER, |
| | ELECTRICAL PLAN REVIEW.PLANS DO NOT |
| | COMPLY WITH FS 471.025 & FAC61G15-23.002 |
| | |
| | 2.INDICATE IF THE EQUIPMENT IS NEW OR |
| | EXISTING.PROVIDE EQUIPMENT SCHEDULE. |
| | |
| | 3.PROVIDE OUTSIDE AIR CALCULATIONS AS |
| | PER 2001 FBC(M) 403.3. |
| | |
| | 4.PROVIDE AIRBALANCE SCHEDULE IN |
| | ACCORDANCE WITH 2001 FBC(M) 501.4. |
| | |
| | 5.ADDITIONAL PERMITS REQUIRED FOR |
| | HOOD, FIRE SUPPRESSION AND WALK-IN |
| | COOLERS.PROVIDE PLANS AND MANUFACTURER |
| | SUBMITTAL DATA WITH PERMIT APPLICATION. |
| | |
| | 6.PROVIDE ADDITIONAL INFORMATION ON |
| | THE VENTILATION FOR THE SMOKER ROOM. |
| | PROVIDE SUBMITTAL FOR THE SMOKER. |
| | |
| | 7.INDICATE CONDENSATE LINE SIZE, PIPE |
| | MATERIAL, AND TERMINATION. |
| | |
| | 8.PROVIDE CURB DETAIL FOR RTU'S. |
| | MINIMUM OF 8" ABOVE THE ROOF SURFACE |
| | REQUIRED PER 2001 FBC 1511.7. |
| | |
| | 9.INDICATE IF THE CONDENSER FOR THE |
| | WALK-IN COOLER IS REMOTE OR PACKAGE. |
| | REMOTE CONDENSERS LOCATED ON THE ROOF |
| | SHALL COMPLY WITH 2001 FBC 1511.7. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561) 805-6719. |