Plan Review Notes
Plan Review Notes For Permit 04060361
Permit Number 04060361
Review Stop M
Sequence Number 1
Notes
Date Text
2004-06-22 00:00:00DENIED:
 1.SEE COMMENT #1 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.PLANS DO NOT
 COMPLY WITH FS 471.025 & FAC61G15-23.002
  
 2.INDICATE IF THE EQUIPMENT IS NEW OR
 EXISTING.PROVIDE EQUIPMENT SCHEDULE.
  
 3.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC(M) 403.3.
  
 4.PROVIDE AIRBALANCE SCHEDULE IN
 ACCORDANCE WITH 2001 FBC(M) 501.4.
  
 5.ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPPRESSION AND WALK-IN
 COOLERS.PROVIDE PLANS AND MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 6.PROVIDE ADDITIONAL INFORMATION ON
 THE VENTILATION FOR THE SMOKER ROOM.
 PROVIDE SUBMITTAL FOR THE SMOKER.
  
 7.INDICATE CONDENSATE LINE SIZE, PIPE
 MATERIAL, AND TERMINATION.
  
 8.PROVIDE CURB DETAIL FOR RTU'S.
 MINIMUM OF 8" ABOVE THE ROOF SURFACE
 REQUIRED PER 2001 FBC 1511.7.
  
 9.INDICATE IF THE CONDENSER FOR THE
 WALK-IN COOLER IS REMOTE OR PACKAGE.
 REMOTE CONDENSERS LOCATED ON THE ROOF
 SHALL COMPLY WITH 2001 FBC 1511.7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.