| Plan Review Notes For Permit 04060361 |
| Permit Number |
04060361 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-10 00:00:00 | 1) SITE PLAN DOES NOT DISPLAY | | | LOCATIONS OF ANY EXISTING OR NEW | | | FIRE HYDRANTS. | | | | | | 2) PANIC HARDWARE REQUIRED ON ALL | | | EXIT DOORS AS NOTED ON THE DOOR | | | SCHEDULE SUBJECT TO 100 OR MORE PERSONS. | | | | | | 3) BUILDING ADDRESS REQUIRED. A MINIMUM | | | OF 6" HIGH NUMBERS ARE REQUIRED. | | | | | | 4) PLEASE PROVIDE PRESCRIPTIVE | | | STRENGTH REQUIREMENTS FOR HANDRAILS | | | AND GUARDRAILS. | | | | | | 5) SOME ELECTRICAL DRAWINGS HAVE | | | DOORS SWINGING IN THE WRONG DIRECTION. | | | | | | 6) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 7) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR HOOD, DUCT, AND SUPPRESSION SYSTEM. | | | | | | 8) EXIT SIGN DIRECTS PERSONS TO | | | OUTDOOR DINING BUT SOME PLANS ARE | | | MISSING THE EXIT DOOR. | | | | | | 9) PLEASE PROVIDE DETAILS ON EXIT | | | DISCHARGE LOCATIONS. | | | | | | 10) EXIT DOOR IS SHOWN THRU SMOKER | | | ROOM. WHAT EQUIPMENT AND ACTIVITIES | | | OCCUR. IS THIS AREA CONSIDERED MORE | | | DANGEROUS THAN THE DINING ROOM. | | | | | | 11) PLEASE INDICATE FIRE EXTINGUISHER | | | LOCATIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|