| 2004-06-14 00:00:00 | ************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE THAT ONE SET OF MEP |
| | PLANS HAVE BEEN RETAINED FOR FILE. |
| | NOTICE HAS BEEN GIVEN ON PREVIOUS REVIEW |
| | -S TO INCLUDE ALL LICENSE # 'S AS |
| | REQUIRED BY FAC 61G15-23.002 ANDFS471. |
| | 023. WE HAVE BEEN IN CONTACT WITH DBPR |
| | AND FBPE'S AND METRO DESIGN GROUP INC |
| | DOES NOT CONTAIN LICENSE #(S) AS REQ'D. |
| | |
| | 2)NOTE: PLEASE SEE PLANS ARE NOT COM- |
| | -PLETE AT THIS TIME FOR FULL REVIEW. |
| | PLEASE SUBMIT PANE SCHEDULES TO CORRE- |
| | -LATE WITH CIRCUITING SHOWN ON PLANS. |
| | PLEASE INCLUDE LOAD CALCULATIONS AND |
| | INFORMATION ON SERVICE. NEW OR EXSITING? |
| | |
| | 3)NOTE: IF SERVICE IS NEW, PLEASE SUBMIT |
| | AIC RATING FOR ALL NEW EQUIPMENT. 110.9 |
| | |
| | 4)NOTE: PLEASE GIVE INFORMATION ON GFI |
| | PROTECTION FOR KITCHEN RECEPTS ARE |
| | REQUIRED UNDER THE 2002 NEC. 210.8B3 |
| | |
| | 5)NOTE: PLEASE SEE 210.63 FOR REQUIRED |
| | RECEPTS FOR RT EQUIPMENT. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | AS THEY MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |