Plan Review Notes
Plan Review Notes For Permit 04060361
Permit Number 04060361
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-14 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SEE THAT ONE SET OF MEP
 PLANS HAVE BEEN RETAINED FOR FILE.
 NOTICE HAS BEEN GIVEN ON PREVIOUS REVIEW
 -S TO INCLUDE ALL LICENSE # 'S AS
 REQUIRED BY FAC 61G15-23.002 ANDFS471.
 023. WE HAVE BEEN IN CONTACT WITH DBPR
 AND FBPE'S AND METRO DESIGN GROUP INC
 DOES NOT CONTAIN LICENSE #(S) AS REQ'D.
  
 2)NOTE: PLEASE SEE PLANS ARE NOT COM-
 -PLETE AT THIS TIME FOR FULL REVIEW.
 PLEASE SUBMIT PANE SCHEDULES TO CORRE-
 -LATE WITH CIRCUITING SHOWN ON PLANS.
 PLEASE INCLUDE LOAD CALCULATIONS AND
 INFORMATION ON SERVICE. NEW OR EXSITING?
  
 3)NOTE: IF SERVICE IS NEW, PLEASE SUBMIT
 AIC RATING FOR ALL NEW EQUIPMENT. 110.9
  
 4)NOTE: PLEASE GIVE INFORMATION ON GFI
 PROTECTION FOR KITCHEN RECEPTS ARE
 REQUIRED UNDER THE 2002 NEC. 210.8B3
  
 5)NOTE: PLEASE SEE 210.63 FOR REQUIRED
 RECEPTS FOR RT EQUIPMENT.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]