| 2005-03-14 00:00:00 | ******* UNSAT ******* |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G15-23.002, |
| | PLEASE INCLUDE ALL INFORMATION ON TITLE |
| | BLOCK AS REQUIRED. |
| | PLEASE SEE THIS WAS NOTED ON ALL |
| | PREVIOUS REVIEWS ON LAST THREE |
| | ELECTRICAL REVIEWS. |
| | THIS IS REQUIRED FOR ALL TRADES AND FOR |
| | ALL SHEETS WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE INCLUDE NOTE FOR REQUIRED |
| | GFI PROTECTION. PLEASE SEE SECTION |
| | 210.8(B)(3) IS NEW FOR THE 2002 CODE AND |
| | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT |
| | RECEPTACLES IN NONDWELLING-TYPE KITCHENS |
| | TO BE GFCI PROTECTED. THIS REQUIREMENT |
| | APPLIES TO EACH AND EVERY 15- AND |
| | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, |
| | WHETHER OR NOT THE RECEPTACLE SERVES |
| | COUNTERTOP APPLIANCES. |
| | |
| | 3)NOTE: PLEASE SEE TITLE AREA ON PLANS |
| | FOR REVISIONS. PLEASE SEE NEW REVISION |
| | IS INDICATED AS # 7 AND PREVIOUS |
| | REVISION WAS REV #1? PLEASE VERIFY |
| | REVISIONS #2-#6?? PLEASE SHOW AND |
| | INDICATE ANY OTHER REV'S. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |