2004-10-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 PLUMBING
  
 1) STAMPED SHEETS FROM DBPR RESTURANT &
 HOTEL DIVISION ARE REQUIRED IN EACH SET
 OF PLANS WITH THE WORKSHEETS FROM DBPR
 INCLUDED. SECTION 101.4.7
 2) APPROVAL SHEET FROM RODNEY COMPO FOR
 THE GREASE INTECEPTOR REQUIRED. WASTE
 ORD. 2938-96
 3) WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9 SHALL BE SHOWN ON THE
 WATER RISER DIAGRAM. (AT ICE MAKER, AND
 DISH WASHER). W.H.A.'S SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE
 NOT IN THE CEILING. PDI-WH 201.
 4) GAS REQUIREMENTS: - THE DOUBLE RACK
 OVEN DOES NOT SHOW A GAS LISTING. UL
 LISTING DOES NOT ADDRESS GAS CONCERNS. -
 FIRE PLACE MANUF. SHEET SHOWS 17,OOO BTU
 MAXIMUM INPUT, BUT GAS RISER SHOWS
 30,000 BTU. PLEASE CLARIFY. - MANUF.
 SHEET FOR THE SF-1 UNIT ON THE ROOM &
 THE WATER HEATER ARE NOT SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]