| Plan Review Notes For Permit 04060338 |
| Permit Number |
04060338 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-10-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | FBC-2001 PLUMBING | | | | | | 1) STAMPED SHEETS FROM DBPR RESTURANT & | | | HOTEL DIVISION ARE REQUIRED IN EACH SET | | | OF PLANS WITH THE WORKSHEETS FROM DBPR | | | INCLUDED. SECTION 101.4.7 | | | 2) APPROVAL SHEET FROM RODNEY COMPO FOR | | | THE GREASE INTECEPTOR REQUIRED. WASTE | | | ORD. 2938-96 | | | 3) WATER HAMMER ARRESTORS REQUIRED BY | | | SECTION 604.9 SHALL BE SHOWN ON THE | | | WATER RISER DIAGRAM. (AT ICE MAKER, AND | | | DISH WASHER). W.H.A.'S SHALL BE LOCATED | | | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE | | | NOT IN THE CEILING. PDI-WH 201. | | | 4) GAS REQUIREMENTS: - THE DOUBLE RACK | | | OVEN DOES NOT SHOW A GAS LISTING. UL | | | LISTING DOES NOT ADDRESS GAS CONCERNS. - | | | FIRE PLACE MANUF. SHEET SHOWS 17,OOO BTU | | | MAXIMUM INPUT, BUT GAS RISER SHOWS | | | 30,000 BTU. PLEASE CLARIFY. - MANUF. | | | SHEET FOR THE SF-1 UNIT ON THE ROOM & | | | THE WATER HEATER ARE NOT SUBMITTED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|