Plan Review Notes
Plan Review Notes For Permit 04060338
Permit Number 04060338
Review Stop P
Sequence Number 2
Notes
Date Text
2004-09-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESS-
 ED, OR NOT ADDRESSED PROPERLY. THE SAME
 COMMENT NUMBER WILL BE USED FROM THE
 FIRST REVIEW TO AVOID CONFUSION.
 6) BOTY SETS OF PLANS SHALL BE SIGNED -
 SEALED & DATED BY THE ARCHITECT OR ENG-
 INEER AS REQUIRED BY FAC 61G1-16.003 OR
 61G15-23.002 & FS 481.2055 OR FS 471.025
 SOME SHEETS HAVE NOT BEEN SIGNED/SEALED/
 DATED.
 8) SHT P0 SEC 15000 PLUMBING (3)(D) AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 NOTES. PDI-WH 201. THIS NOTE HAS NOT
 BEEN DELETED.
 10) NO REPLY FROM RODNEY COMPO CONCERN-
 ING GREASE INTECEPTOR RECIEVED. WASTE
 ORD. 2938-96 (561) 837-4074.
 12) INFORMATION REQUIRED FOR GAS PERMIT
 B) SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED.
 14) SHT P3 WATER ISOMETRIC, WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIX-
 TURES IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS. - STILL SHOWN
 IN CEILING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]