| Plan Review Notes For Permit 04060338 |
| Permit Number |
04060338 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-09-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | THE FOLLOWING COMMENTS WERE NOT ADDRESS- | | | ED, OR NOT ADDRESSED PROPERLY. THE SAME | | | COMMENT NUMBER WILL BE USED FROM THE | | | FIRST REVIEW TO AVOID CONFUSION. | | | 6) BOTY SETS OF PLANS SHALL BE SIGNED - | | | SEALED & DATED BY THE ARCHITECT OR ENG- | | | INEER AS REQUIRED BY FAC 61G1-16.003 OR | | | 61G15-23.002 & FS 481.2055 OR FS 471.025 | | | SOME SHEETS HAVE NOT BEEN SIGNED/SEALED/ | | | DATED. | | | 8) SHT P0 SEC 15000 PLUMBING (3)(D) AIR | | | CHAMBERS ARE NOT APPROVED. DELETE FROM | | | NOTES. PDI-WH 201. THIS NOTE HAS NOT | | | BEEN DELETED. | | | 10) NO REPLY FROM RODNEY COMPO CONCERN- | | | ING GREASE INTECEPTOR RECIEVED. WASTE | | | ORD. 2938-96 (561) 837-4074. | | | 12) INFORMATION REQUIRED FOR GAS PERMIT | | | B) SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED. | | | 14) SHT P3 WATER ISOMETRIC, WATER HAMMER | | | ARRESTORS SHALL BE LOCATED NEAR THE FIX- | | | TURES IN AN "EFFECTIVE RANGE" NOT IN THE | | | CEILING AS SHOWN. PDI-WH 201 & MANUF. | | | INSTALLATION INSTRUCTIONS. - STILL SHOWN | | | IN CEILING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|