| Plan Review Notes For Permit 04060338 |
| Permit Number |
04060338 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-08-31 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALC BEFORE ISSUANCE. | | | | | | 2.)DOOR #2 LACKS THE MANEUVERING | | | CLEARANCE REQUIRED BY FBC11 FIGURE 25 | | | (MIN 12", PLAN SHOWS 7 1/2").REVISE | | | AFFECTED SHEETS. | | | | | | 3.)PROVIDE LOADING INFORMATION FOR | | | THE SHUTTER STORAGE, A4.2.SHOW THAT | | | THE EXISTING TRUSSES CAN ACCOMODATE THIS | | | ADDITIONAL LOAD. | | | | | | 4.)THERE IS A STRUCTURAL MULLION FOR | | | THE STOREFRONT SYSTEM THAT DOES NOT | | | APPEAR TO BE INCLUDED IN THE NOA | | | (ANGLED APPLICATION).ADDRESS. | | | | | | 5.)SOME SHEETS ARE NOT SIGNED, SEALED | | | AND DATED (EC1, EC2, EC3, A2.3, A3, A6.2 | | | A7, A7.1, A8, A9, A9.1, M0, M3, M4, M5, | | | P0, E0, E1, E4, E6), ONE SET. | | | | | | 6.)FLORIDA STATE OR LOCAL PRODUCT | | | APPROVAL REQUIRED IN ADDITION TO THE | | | TEST REPORT.WWW.FLORIDABUILDING.ORG | | | THIS IS REQUIRED FOR ALL OF THE DADE | | | COUNTY NOAS. |
|