2004-08-31 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC BEFORE ISSUANCE.
  
 2.)DOOR #2 LACKS THE MANEUVERING
 CLEARANCE REQUIRED BY FBC11 FIGURE 25
 (MIN 12", PLAN SHOWS 7 1/2").REVISE
 AFFECTED SHEETS.
  
 3.)PROVIDE LOADING INFORMATION FOR
 THE SHUTTER STORAGE, A4.2.SHOW THAT
 THE EXISTING TRUSSES CAN ACCOMODATE THIS
 ADDITIONAL LOAD.
  
 4.)THERE IS A STRUCTURAL MULLION FOR
 THE STOREFRONT SYSTEM THAT DOES NOT
 APPEAR TO BE INCLUDED IN THE NOA
 (ANGLED APPLICATION).ADDRESS.
  
 5.)SOME SHEETS ARE NOT SIGNED, SEALED
 AND DATED (EC1, EC2, EC3, A2.3, A3, A6.2
 A7, A7.1, A8, A9, A9.1, M0, M3, M4, M5,
 P0, E0, E1, E4, E6), ONE SET.
  
 6.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE
 TEST REPORT.WWW.FLORIDABUILDING.ORG
 THIS IS REQUIRED FOR ALL OF THE DADE
 COUNTY NOAS.