| Date |
Text |
| 2004-07-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) PLANS HAVE BEEN ROUTED TO THE DBPR |
| | HOTEL AND RESTURANT DIVISION. THE TWO |
| | PAGE WORKSHEETS RETURNED FROM DBPR SHALL |
| | BE ATTACHED TO EACH SET OF PLANS FOR RE- |
| | VIEW. SECTIONS 101.4.7 & 104.2.1. |
| | 2) SUBMIT CALCULATIONS FOR MINIMUM FAC- |
| | ILITIES PER TABLES 1003.1 & 403.1. INDI- |
| | CATE IF SEATING IS FIXED OR NOT FIXED. |
| | 3) SHT D1, ALL CAPPED AND/OR ABANDONED |
| | PLUMBING PIPING SHALL BE INSPECTED PRIOR |
| | TO COVERING. NO DEAD ENDS ALLOWED PER |
| | SECTION 704.5 |
| | 4) SHT A2.2 KEYED NOTES: #11 STATES FLUE |
| | TO BE A MINIMUM OF 2' FROM VERTICAL WALL |
| | BUT FUEL GAS SECTION 506.6.2 REQUIRES A |
| | MINIMUM OF 8' FROM VERTICAL WALLS. NOTE |
| | #11 ALSO STATES 1' ABOVE ROOF, BUT CODE |
| | SECTION 506.6.2 STATES THE VENT SHALL |
| | TERMINATE NOT LESS THAN 2 FEET HIGHER |
| | THAN ANY PORTION OF A BUILDING WITHIN 10 |
| | FEET. SEE DETAIL 17 ON SHT A7.1 |
| | 5) SUBMIT MANUF. SPECIFICATION/INSTALL- |
| | ATION SHEETS FOR THE FIREPLACE AND THE |
| | VENTING SYSTEM. |
| | 6) BOTH SETS OF PLANS SHALL BE SIGNED - |
| | SEALED & DATED BY THE ARCHITECT/ENGINEER |
| | OF RECORD. FAC 61G1-16.003/61G15-23.002 |
| | FS 481.2055/471.025. |
| | 7) SHT P0 DETAIL #2 FILTERS SHALL BE |
| | "NSF" COMPLIANT. SUBMIT MANUF. SPECIFIC- |
| | ATION SHEETS. |
| | 8) SHT P0 SEC 15000 PLUMBING (3)(D) AIR |
| | CHAMBERS ARE NOT APPROVED. DELETE FROM |
| | NOTES. PDI-WH 201. |
| | 9) P0 GENERAL NOTES #4 ADOPTED CODE IS |
| | FLA. BUILDING CODE - 2001 PLUMBING, NOT |
| | SBCCI-94 STANDARD PLUMBING CODE AS INDI- |
| | CATED. UPDATE GENERAL NOTES. SEC 104.2.1 |
| | 10) GREASE INTERCEPTOR SHALL BE SIZED BY |
| | RODNEY COMPO ENVIRONMENTAL COMPLIANCE. |
| | PLEASE CONTACT HIM AT (561) 837-4074. |
| | WASTE ORD. #2938-96. |
| | 11) RPZ BACKFLOW REQUIRED ON THE WATER |
| | SERVICE. SECTION 608.13.2 |
| | 12) FOLLOWING INFORMATION REQUIRED FOR |
| | GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | - SHT P2 PLAN NOTES #9 INDICATES 7" TO |
| | 12" WATER COLUMN - CHARTS IN FBC-2001 |
| | FUEL GAS ARE FOR 12" TO 14" WATER COLUMN |
| | WHICH IS 1/2 LB. PRESSURE. PLEASE VERIFY |
| | DELIVERY PRESSURE WITH FUEL PROVIDER. |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | 13) DISHWASHER (27A) SHALL DRAIN INTO |
| | THE SANITARY SYSTEM, NOT THE GREASE SYS- |
| | TEM. PER UTILITY DEPT. |
| | 14) SHT P3 WATER ISOMETRIC, AIR CHAMB- |
| | ERS ARE NOT APPROVED. WATER HAMMER ARR- |
| | ESTORS REQUIRED BY SECTION 604.9 SHALL |
| | BE INSTALLED NEAR THE FIXTURES IN AN |
| | "EFFICTIVE RANGE" NOT IN THE CEILING. |
| | PDI-WH 201 & MANUF. INSTALLATION INSTR. |
| | 15) SHT P3 WATER ISOMETRIC, A SHUT OFF |
| | VALVE IS REQUIRED ON SUPPLY LINE TO HOSE |
| | BIBB. SECTION 606.2(2). |
| | 15) SHTS P1 & P5. ITEMS NOT FOUND ON SHT |
| | P1 BUT SHOWN ON KITCHEN EQUIPMENT SCHED- |
| | ULE. ITEMS 13, 21C, 23, 23B, 54, 58, AND |
| | 61. - ALSO CLAIRFY ITEM 72A SHOWN ON |
| | SCHEDULE AS DECK OVEN, BUT ON FLOOR PLAN |
| | IT IS IN THE FREEZER. PLEASE CORRELATE |
| | PLANS TO SCHEDULE. |
| | 16) SHT P1, PLAN NOTES #6 INDICATES THAT |
| | FLOOR DRAINS ARE BEING USED FOR INDIRECT |
| | WASTE. THIS IS NOT APPROVED. FLOOR SINKS |
| | OR HUB DRAINS ARE REQUIRED FOR INDIRECT |
| | WASTE. FLOOR DRAINS ARE NOT AN APPROVED |
| | INDIRECT WASTE RECEPTOR. SECTIONS 802.3 |
| | AND 802.3.2. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |