Plan Review Notes
Plan Review Notes For Permit 04060338
Permit Number 04060338
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PLANS HAVE BEEN ROUTED TO THE DBPR
 HOTEL AND RESTURANT DIVISION. THE TWO
 PAGE WORKSHEETS RETURNED FROM DBPR SHALL
 BE ATTACHED TO EACH SET OF PLANS FOR RE-
 VIEW. SECTIONS 101.4.7 & 104.2.1.
 2) SUBMIT CALCULATIONS FOR MINIMUM FAC-
 ILITIES PER TABLES 1003.1 & 403.1. INDI-
 CATE IF SEATING IS FIXED OR NOT FIXED.
 3) SHT D1, ALL CAPPED AND/OR ABANDONED
 PLUMBING PIPING SHALL BE INSPECTED PRIOR
 TO COVERING. NO DEAD ENDS ALLOWED PER
 SECTION 704.5
 4) SHT A2.2 KEYED NOTES: #11 STATES FLUE
 TO BE A MINIMUM OF 2' FROM VERTICAL WALL
 BUT FUEL GAS SECTION 506.6.2 REQUIRES A
 MINIMUM OF 8' FROM VERTICAL WALLS. NOTE
 #11 ALSO STATES 1' ABOVE ROOF, BUT CODE
 SECTION 506.6.2 STATES THE VENT SHALL
 TERMINATE NOT LESS THAN 2 FEET HIGHER
 THAN ANY PORTION OF A BUILDING WITHIN 10
 FEET. SEE DETAIL 17 ON SHT A7.1
 5) SUBMIT MANUF. SPECIFICATION/INSTALL-
 ATION SHEETS FOR THE FIREPLACE AND THE
 VENTING SYSTEM.
 6) BOTH SETS OF PLANS SHALL BE SIGNED -
 SEALED & DATED BY THE ARCHITECT/ENGINEER
 OF RECORD. FAC 61G1-16.003/61G15-23.002
 FS 481.2055/471.025.
 7) SHT P0 DETAIL #2 FILTERS SHALL BE
 "NSF" COMPLIANT. SUBMIT MANUF. SPECIFIC-
 ATION SHEETS.
 8) SHT P0 SEC 15000 PLUMBING (3)(D) AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 NOTES. PDI-WH 201.
 9) P0 GENERAL NOTES #4 ADOPTED CODE IS
 FLA. BUILDING CODE - 2001 PLUMBING, NOT
 SBCCI-94 STANDARD PLUMBING CODE AS INDI-
 CATED. UPDATE GENERAL NOTES. SEC 104.2.1
 10) GREASE INTERCEPTOR SHALL BE SIZED BY
 RODNEY COMPO ENVIRONMENTAL COMPLIANCE.
 PLEASE CONTACT HIM AT (561) 837-4074.
 WASTE ORD. #2938-96.
 11) RPZ BACKFLOW REQUIRED ON THE WATER
 SERVICE. SECTION 608.13.2
 12) FOLLOWING INFORMATION REQUIRED FOR
 GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 - SHT P2 PLAN NOTES #9 INDICATES 7" TO
 12" WATER COLUMN - CHARTS IN FBC-2001
 FUEL GAS ARE FOR 12" TO 14" WATER COLUMN
 WHICH IS 1/2 LB. PRESSURE. PLEASE VERIFY
 DELIVERY PRESSURE WITH FUEL PROVIDER.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 13) DISHWASHER (27A) SHALL DRAIN INTO
 THE SANITARY SYSTEM, NOT THE GREASE SYS-
 TEM. PER UTILITY DEPT.
 14) SHT P3 WATER ISOMETRIC, AIR CHAMB-
 ERS ARE NOT APPROVED. WATER HAMMER ARR-
 ESTORS REQUIRED BY SECTION 604.9 SHALL
 BE INSTALLED NEAR THE FIXTURES IN AN
 "EFFICTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201 & MANUF. INSTALLATION INSTR.
 15) SHT P3 WATER ISOMETRIC, A SHUT OFF
 VALVE IS REQUIRED ON SUPPLY LINE TO HOSE
 BIBB. SECTION 606.2(2).
 15) SHTS P1 & P5. ITEMS NOT FOUND ON SHT
 P1 BUT SHOWN ON KITCHEN EQUIPMENT SCHED-
 ULE. ITEMS 13, 21C, 23, 23B, 54, 58, AND
 61. - ALSO CLAIRFY ITEM 72A SHOWN ON
 SCHEDULE AS DECK OVEN, BUT ON FLOOR PLAN
 IT IS IN THE FREEZER. PLEASE CORRELATE
 PLANS TO SCHEDULE.
 16) SHT P1, PLAN NOTES #6 INDICATES THAT
 FLOOR DRAINS ARE BEING USED FOR INDIRECT
 WASTE. THIS IS NOT APPROVED. FLOOR SINKS
 OR HUB DRAINS ARE REQUIRED FOR INDIRECT
 WASTE. FLOOR DRAINS ARE NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. SECTIONS 802.3
 AND 802.3.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]