| 2004-06-15 00:00:00 | *************** UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE INCLUDE ALL INFORMATION |
| | ON TITLE BLOCKS AS REQUIRED UNDER |
| | FAC 61G15-23.002/ 61G1-16.004 |
| | PLEASE INCLUDE ALL NAMES AND LICENSE #'S |
| | |
| | PLEASE ALOS SEE ONLY ONE SET OF PLANS |
| | ARE SIGNED, DATED AND SEALED AS REQUIRED |
| | UNDER FS 471.025/ 61G15-23.002 |
| | |
| | 2)NOTE: PLEASE VERIFY REQUIRED SIGN |
| | CIRCUIT PER 600.5 |
| | |
| | 3)NOTE: PLEASE SEE PANEL "P1", SHOWS |
| | A PANEL "ILG", YET RISER SHOWS "IGP". |
| | (MISPRINT) |
| | |
| | 4)NOTE: PLEASE PROVIDE COMPLETE LOAD |
| | CALCULATION ON EXISTING SERVICE AND |
| | SEC'S. SOME OF THE SERVICES ON THIS |
| | MALL ARE IN DANGER OF HEATED CONDUCTORS |
| | AND OVERLOADED SERVICES AND SOME |
| | SEEM TO BE "MAXED" OUT AND CLOSE TO |
| | BEING OVERLOADED AT PRESENT TIME. |
| | 215.5/220 |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | AS SOME MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO TWO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |