| 2004-07-13 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC (P2) .PROVIDE THE PRINTED |
| | NAME AND LICENSE NUMBER OF THE PERSON |
| | WHO PREPARED THE ENERGY CALC. |
| | |
| | 2.)FLORIDA STATE, LOCAL OR SITE |
| | SPECIFIC PRODUCT APPROVALS REQUIRED |
| | IN ADDITION TO THE NOAS.PLEASE SEE |
| | WWW.FLORIDABUILDING.ORG (PRODUCT |
| | APPROVAL) FOR MORE INFORMATION. |
| | |
| | 3.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE |
| | A PERMIT CAN BE ISSUED.FS713.13 |
| | |
| | 4.)THE DOUBLE DOORS 1A AND 1B ARE |
| | REQUIRED TO COMPLY WITH FBC11-4.13.7 |
| | (MINIMUM OF 48" PLUS THE WIDTH OF THE |
| | DOOR), FIGURE 26(A). |
| | |
| | 5.)REGARDING DOORS #7 AND #2 (SERVICE& |
| | COMMUNITY ROOM) DOUBLE LEAF DOORS ARE |
| | TO COMPLY WITH 11-4.13.4 AND 11-4.13.5. |
| | |
| | 6.)THE DOOR TO THE WOMEN'S |
| | ACCESSIBLE STALL IS TO HAVE THE |
| | MANUEVERING CLEARANCE AS REQUIRED BY |
| | FBC11-4.13.6, FBC11-4.23.2, FIGURE 25. |
| | |
| | 7.)PROVIDE INFORMATION AS TO WHERE |
| | AND HOW THE HURRICANE SHUTTERS WILL BE |
| | STORED.IF THEY ARE STORED VERTICALLY, |
| | PROVIDE A STRUCTURAL RACK DETAIL. |
| | |
| | 8.)THE PRODUCT APPROVAL FOR DOOR #6, |
| | THE STEEL ENTRY DOOR, HAS A PRODUCT |
| | LIMITATION 3.2, UNIT SHALL BE INSTALLED |
| | ONLY AT LOCATIONS PROTECTED BY A CANOPY |
| | OR OVERHANG SUCH THAT THE ANGLE BETWEEN |
| | THE EDGE OF CANOPY OR OVERHANG TO SILL |
| | IS LESS THAN 45 DEGREES.ADDRESS. |
| | |
| | 9.)PROVIDE PRODUCT APPROVALS FOR THE |
| | ENTRY DOORS #1A AND #5. |
| | |
| | 10.) PROVIDE A HURRICANE SHUTTER |
| | ATTACHMENT SCHEDULE, SEE ATTACHED FORM. |
| | IF NOT PROVIDED BEFORE PERMIT ISSUANCE, |
| | THE SHUTTERS WILL REQUIRE A SEPARATE |
| | PERMIT. |
| | |
| | 11.) ANY PRODUCT APPROVALS REQUIRED BUT |
| | NOT SUBMITTED PROPERLY BEFORE ISSUANCE |
| | WILL REQUIRE SEPARATE PERMITS FOR THOSE |
| | ITEMS. |
| | |
| | 12.) IT APPEARS THAT THERE IS A |
| | STRUCTURAL ANGLED MULLION AT DOOR #1A. |
| | PLEASE PROVIDE PRODUCT APPROVAL/TEST |
| | REPORTS. |
| | |
| | 13.)SEPARATE PERMITS REQUIRED FOR THE |
| | SIGNS. |
| | |
| | 14.)PROVIDE SIGNAGE TO COMPLY WITH |
| | FBC704.2.1.4; NOTE ON PLAN. |
| | |
| | 15.)PROVIDE A LOCATION FOR THE |
| | STORAGE OF THE HURRICANE SHUTTERS. |