Date Text
2004-06-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHTS 5 0F 9, IRR 1, AND IRR 3. SHEET
 5 OF 9 SHOWS WATER METERS AND BACKFLOWS
 FOR IRRIGATION, BUT SHEETS IRR. 1 & 3
 INDICATE 2" WELLS FOR IRRIGATION WATER.
 PLEASE CLARIFY AND CORRELATE PLANS.
 WELL PERMITS SHALL BE ISSUED BY PALM BCH
 HEALTH DEPT. SECTION 104.2.1
 2) SHT A-1 SHOW CLEAR FLOOR SPACE FOR
 THE URINAL. SECTION 11-4.18.3
 3) SHT P-2 CONDENSATE LINE SHALL HAVE A
 RELIEF VENT (GOOSE NECK) INSTALLED AS
 THE CONDENSATE LINE EXITS THE BLDG.
 SECTION 104.2.1
 4) SHT P-3 WATER PIPING NOTES: #4, DI-
 ELECTRIC UNIONS NOT APPROVED FOR WATER
 DISTRIBUTION PIPING. DELETE REFERENCE OR
 MODIFY NOTE TO READ "DIELECTRIC COUPLING
 SECTION 104.2.1
 5) FOLLOWING INFORMATION FOR ENGINEER:
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025 - INITIALS ARE NOT APPROVED
 FULL SIGNATURE REQUIRED, MINIMUM FIRST
 AND LAST NAME REQUIRED.
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 -- SEAL SHOWS FIST NAME DAVOOD, BUT THE
 TITLE BLOCK SHOWS FIRST NAME AS DAVID.
 CORRELATE NAME ON SEAL AND NAME ON TITLE
 BLOCK.
  